| Assessment Year | 2014 |
|---|---|
| Principal Product | Airport Products |
| NAICS | 332999: All Other Miscellaneous Fabricated Metal Product Manufacturing |
| SIC | 3999: Manufacturing Industries, Not Elsewhere Classified |
| Sales Range | $100 M to 500M |
| # of Employees | 312 |
| Plant Area |
215,000
ft2
|
| Annual Production | 468
units
|
| Production Hrs. Annual | 2,125
hrs
|
| Location (State) | Utah |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $122,043 | 3,416,400 |
kWh
|
$0.036 |
| Electricity Demand | $188,902 | 12,013 |
kW-mo/yr
|
$15.72 |
| Electricity Fees | $4,344 | - |
|
- |
| Natural Gas | $190,010 | 43,692 |
MMBtu
|
$4.35 |
| LPG | $17,537 | 988 |
MMBtu
|
$17.75 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $169,598 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $15,995 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.3212: Optimize plant power factor | $10,406 | $20,000 | - | - | $10,406 | - | |
| 02 | 2.4322: Use or replace with energy efficient substitutes | $74,212 | $31,860 |
$24,162
676,372
kWh
|
$50,050
-
kW-mo/yr
|
- | - | |
| 03 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $53,966 | $45,410 |
$18,377
514,429
kWh
|
- | - |
$35,589
-
MMBtu
|
|
| 04 | 2.7243: Improve air circulation with destratification fans / other methods | $14,073 | $49,835 |
$(-222.8)
(-6,237)
kWh
|
$(-490.4)
-
kW-mo/yr
|
- |
$14,786
-
MMBtu
|
|
| 05 | 2.6218: Turn off equipment when not in use | $7,083 | $304 | - | - | - |
$7,083
-
MMBtu
|
|
| 06 | 2.7491: Insulate glazing, walls, ceilings, and roofs | $2,513 | $2,503 | - | - | - |
$2,513
-
MMBtu
|
|
| 07 | 2.7241: Install outside air damper / economizer on hvac unit | $946 | $2,100 |
$946
26,484
kWh
|
- | - | - | |
| 08 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $4,850 | $255 |
$4,850
135,780
kWh
|
- | - | - | |
| 09 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,549 | $4,061 |
$544
15,234
kWh
|
$1,005
-
kW-mo/yr
|
- | - | |
| TOTAL RECOMMENDED | $169,598 | $156,328 |
$48,656
1,362,062
kWh
|
$50,565
-
kW-mo/yr
|
$10,406 |
$59,971
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $15,995 | $7,123 |
$5,394
151,014
kWh
|
$1,005
-
kW-mo/yr
|
- |
$9,596
-
MMBtu
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | |||