Assessment Year | 2016 |
---|---|
Principal Product | Pet foods, dried fruit, baby foods |
NAICS | 311111: Dog and Cat Food Manufacturing |
SIC | 2047: Dog and Cat Food |
Sales Range | $10 M to 50M |
# of Employees | 150 |
Plant Area |
115,000
ft2
|
Annual Production | 50,000,000
lb
|
Production Hrs. Annual | 6,760
hrs
|
Location (State) | Illinois |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $133,205 | 2,419,096 |
kWh
|
$0.055 |
Electricity Demand | $39,470 | 6,221 |
kW-mo/yr
|
$6.34 |
Electricity Fees | $1,520 | - |
|
- |
Natural Gas | $10,095 | 1,863 |
MMBtu
|
$5.42 |
LPG | $10,853 | 597 |
MMBtu
|
$18.19 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $14,070 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $1,666 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | LPG Savings |
---|---|---|---|---|---|---|---|
01 | 2.8227: Adjust / maintain fork lift trucks for most efficient operation | $8,603 | $10,500 |
$(-2,250.0)
(-54,600)
kWh
|
- |
$10,853
-
MMBtu
|
|
02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,932 | $50 |
$1,517
36,817
kWh
|
$415
-
kW-mo/yr
|
- | |
03 | 2.3137: Use power during off-peak periods | $915 | $100 | - |
$915
-
kW-mo/yr
|
- | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $902 | $3,944 |
$708
17,188
kWh
|
$194
-
kW-mo/yr
|
- | |
05 | 2.7135: Install occupancy sensors | $764 | $600 |
$672
16,311
kWh
|
$92
-
kW-mo/yr
|
- | |
06 | 2.4133: Use most efficient type of electric motors | $760 | $1,040 |
$557
13,512
kWh
|
$203
-
kW-mo/yr
|
- | |
07 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $194 | $425 |
$142
3,433
kWh
|
$52
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $14,070 | $16,659 |
$1,346
32,661
kWh
|
$1,871
-
kW-mo/yr
|
$10,853
-
MMBtu
|
||
TOTAL IMPLEMENTED | $1,666 | $4,544 |
$1,380
33,499
kWh
|
$286
-
kW-mo/yr
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | LPG Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs