Assessment Year | 2013 |
---|---|
Principal Product | Engineering services |
NAICS | 541330: Engineering Services |
SIC | 8711: Engineering Services |
Sales Range | $500 k to 1M |
# of Employees | 350 |
Plant Area |
64,808
ft2
|
Annual Production | 0
units
|
Production Hrs. Annual | 3,120
hrs
|
Location (State) | Illinois |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $94,944 | 2,387,428 |
kWh
|
$0.040 |
Electricity Demand | $37,423 | 5,951 |
kW-mo/yr
|
$6.29 |
Electricity Fees | $8,598 | - |
|
- |
Fuel Oil #2 | $66,351 | 2,940 |
MMBtu
|
$22.57 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $84,028 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $68,525 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Fuel Oil #2 Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|---|---|
01 | 2.1223: Install smaller boiler (increase high fire duty cycle) | $48,621 | $13,862 | - | - |
$(-17,730.0)
-
MMBtu
|
$66,351
-
MMBtu
|
- | - | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $17,169 | $11,159 |
$11,981
301,052
kWh
|
$5,188
-
kW-mo/yr
|
- | - | - | - | |
03 | 2.1213: Direct warmest air to combustion intake | $15,503 | $11,000 |
$229
5,760
kWh
|
$76
-
kW-mo/yr
|
- |
$15,198
-
MMBtu
|
- | - | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,463 | $1,425 |
$649
16,311
kWh
|
$140
-
kW-mo/yr
|
- | - | $282 | $392 | |
05 | 2.7135: Install occupancy sensors | $1,272 | $1,475 |
$1,272
31,955
kWh
|
- | - | - | - | - | |
TOTAL RECOMMENDED | $84,028 | $38,921 |
$14,131
355,078
kWh
|
$5,404
-
kW-mo/yr
|
$(-17,730.0)
-
MMBtu
|
$81,549
-
MMBtu
|
$282 | $392 | ||
TOTAL IMPLEMENTED | $68,525 | $27,921 |
$13,902
349,318
kWh
|
$5,328
-
kW-mo/yr
|
$(-17,730.0)
-
MMBtu
|
$66,351
-
MMBtu
|
$282 | $392 |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs