| Assessment Year | 2006 |
|---|---|
| Principal Product | Injection molded plastic parts |
| NAICS | 326199: All Other Plastics Product Manufacturing |
| SIC | 3089: Plastics Products, Not Elsewhere Classified |
| Sales Range | $1 M to 5M |
| # of Employees | 39 |
| Plant Area |
20,000
ft2
|
| Annual Production | 15,900,000
pieces
|
| Production Hrs. Annual | 6,240
hrs
|
| Location (State) | Missouri |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $61,736 | 1,268,698 |
kWh
|
$0.049 |
| Electricity Demand | $7,925 | 3,538 |
kW-mo/yr
|
$2.24 |
| Electricity Fees | $15,080 | - |
|
- |
| Natural Gas | $5,385 | 479 |
MMBtu
|
$11.24 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $11,370 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $4,104 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
|---|---|---|---|---|---|---|
| 01 | 2.4133: Use most efficient type of electric motors | $5,936 | $9,020 |
$5,446
111,825
kWh
|
$490
-
kW-mo/yr
|
|
| 02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,061 | $723 |
$1,894
38,878
kWh
|
$167
-
kW-mo/yr
|
|
| 03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,899 | $400 |
$1,787
36,694
kWh
|
$112
-
kW-mo/yr
|
|
| 04 | 2.7135: Install occupancy sensors | $961 | $600 |
$881
18,086
kWh
|
$80
-
kW-mo/yr
|
|
| 05 | 2.4314: Use synthetic lubricant | $369 | $300 |
$340
6,982
kWh
|
$29
-
kW-mo/yr
|
|
| 06 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $144 | - |
$132
2,806
kWh
|
$12
-
kW-mo/yr
|
|
| TOTAL RECOMMENDED | $11,370 | $11,043 |
$10,480
215,271
kWh
|
$890
-
kW-mo/yr
|
||
| TOTAL IMPLEMENTED | $4,104 | $1,123 |
$3,813
78,378
kWh
|
$291
-
kW-mo/yr
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs