Assessment Year | 2001 |
---|---|
Principal Product | Ball and Roller Bearings |
NAICS |
n/a
|
SIC | 3562: Ball and Roller Bearings |
Sales Range | $100 M to 500M |
# of Employees | 200 |
Plant Area |
200,000
ft2
|
Annual Production | 50,000,000
lb
|
Production Hrs. Annual | 7,488
hrs
|
Location (State) | Illinois |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $1,129,879 | 23,817,186 |
kWh
|
$0.047 |
Electricity Demand | $154,676 | 45,515 |
kW-mo/yr
|
$3.40 |
Electricity Fees | $76,826 | - |
|
- |
Natural Gas | $60,593 | 15,304 |
MMBtu
|
$3.96 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $158,131 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.4323: Use optimum size and capacity equipment | $78,182 | $160,000 | n/a |
$70,121
1,479,352
kWh
|
$8,061
-
kW-mo/yr
|
- | - | - |
02 | 2.4221: Install compressor air intakes in coolest locations | $14,963 | $2,000 |
$13,404
282,772
kWh
|
$1,559
-
kW-mo/yr
|
- | - | - | |
03 | 2.7231: Use radiant heater for spot heating | $14,509 | $12,000 | - | - |
$14,509
-
MMBtu
|
- | - | |
04 | 2.4133: Use most efficient type of electric motors | $13,903 | $15,470 | n/a |
$12,799
270,029
kWh
|
$1,104
-
kW-mo/yr
|
- | - | - |
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $9,417 | $4,200 |
$8,446
178,144
kWh
|
$971
-
kW-mo/yr
|
- | - | - | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $6,164 | $5,040 |
$5,626
118,682
kWh
|
$647
-
kW-mo/yr
|
- | - | $(-109.0) | |
07 | 2.7135: Install occupancy sensors | $3,232 | $1,875 |
$2,863
60,396
kWh
|
$369
-
kW-mo/yr
|
- | - | - | |
08 | 2.4239: Eliminate or reduce compressed air usage | $2,848 | $4,000 |
$2,564
54,105
kWh
|
$284
-
kW-mo/yr
|
- | - | - | |
09 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $622 | $593 |
$316
6,656
kWh
|
$31
-
kW-mo/yr
|
- | - | $275 | |
10 | 3.3131: Use evaporation to concentrate material | $11,487 | $27,000 | - | - | - |
$11,487
-
Tgal
|
- | |
11 | 3.4154: Eliminate leaks in water lines and valves | $2,804 | $500 | - | - | - |
$2,804
-
Tgal
|
- | |
TOTAL RECOMMENDED | $158,131 | $232,678 |
$116,139
2,450,136
kWh
|
$13,026
-
kW-mo/yr
|
$14,509
-
MMBtu
|
$14,291
-
Tgal
|
$166 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs