| Assessment Year | 1998 |
|---|---|
| Principal Product | Coated Steel Wire |
| NAICS |
n/a
|
| SIC | 3315: Steel Wiredrawing and Steel Nails and Spikes |
| Sales Range | $5 M to 10M |
| # of Employees | 20 |
| Plant Area |
70,000
ft2
|
| Annual Production | 10,000
ton
|
| Production Hrs. Annual | 6,240
hrs
|
| Location (State) | Illinois |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $47,159 | 896,542 |
kWh
|
$0.053 |
| Electricity Demand | $5,322 | 2,256 |
kW-mo/yr
|
$2.36 |
| Electricity Fees | $1,144 | - |
|
- |
| Natural Gas | $132,677 | 35,199 |
MMBtu
|
$3.77 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $16,868 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Solid Waste (non-haz) Savings | Administrative Changes Savings |
|---|---|---|---|---|---|---|---|---|---|
| 01 | 2.2514: Cover open tanks | $3,808 | $1,100 | n/a | - | - |
$3,808
-
MMBtu
|
- | - |
| 02 | 2.4133: Use most efficient type of electric motors | $2,213 | $4,250 | n/a |
$1,683
44,549
kWh
|
$530
-
kW-mo/yr
|
- | - | - |
| 03 | 2.1213: Direct warmest air to combustion intake | $2,124 | $1,500 | n/a | - | - |
$2,124
-
MMBtu
|
- | - |
| 04 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $1,538 | $3,000 | n/a |
$1,738
48,652
kWh
|
$398
-
kW-mo/yr
|
$(-598.0)
-
MMBtu
|
- | - |
| 05 | 2.4231: Reduce the pressure of compressed air to the minimum required | $768 | - | n/a |
$542
14,361
kWh
|
$226
-
kW-mo/yr
|
- | - | - |
| 06 | 2.7135: Install occupancy sensors | $548 | $400 | n/a |
$382
10,258
kWh
|
$166
-
kW-mo/yr
|
- | - | - |
| 07 | 3.1191: Change procedures / equipment / operating conditions | $4,349 | $1,250 | n/a | - | - | - |
$4,349
-
lb
|
- |
| 08 | 3.5315: Lease / purchase baler; sell cardboard to recycler | $480 | $250 | n/a | - | - | - | - | $480 |
| 09 | 4.821: Pay bills on time to avoid late fees | $1,040 | - | n/a | - | - | - | - | $1,040 |
| TOTAL RECOMMENDED | $16,868 | $11,750 |
$4,345
117,820
kWh
|
$1,320
-
kW-mo/yr
|
$5,334
-
MMBtu
|
$4,349
-
lb
|
$1,520 | ||
| TOTAL IMPLEMENTED | - | - | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Solid Waste (non-haz) Savings | Administrative Changes Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs