| Assessment Year | 1998 |
|---|---|
| Principal Product | Concrete Panels |
| NAICS |
n/a
|
| SIC | 3272: Concrete Products, Except Block and Brick |
| Sales Range | $10 M to 50M |
| # of Employees | 110 |
| Plant Area |
59,000
ft2
|
| Annual Production | 11,000
pieces
|
| Production Hrs. Annual | 3,510
hrs
|
| Location (State) | Illinois |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $30,609 | 681,125 |
kWh
|
$0.045 |
| Electricity Demand | $36,939 | 3,028 |
kW-mo/yr
|
$12.20 |
| Electricity Fees | $425 | - |
|
- |
| Natural Gas | $90,318 | 23,053 |
MMBtu
|
$3.92 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $80,766 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $6,848 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Solid Waste (non-haz) Savings | Administrative Changes Savings |
|---|---|---|---|---|---|---|---|---|---|
| 01 | 2.3192: Use fossil fuel powered generator during peak demand periods | $20,275 | $1,000 |
$9,805
233,880
kWh
|
$25,620
-
kW-mo/yr
|
- | - | $(-15,150.0) | |
| 02 | 2.1213: Direct warmest air to combustion intake | $5,254 | $12,000 | - | - |
$5,254
-
MMBtu
|
- | - | |
| 03 | 2.7135: Install occupancy sensors | $1,019 | $825 |
$499
12,016
kWh
|
$520
-
kW-mo/yr
|
- | - | - | |
| 04 | 2.7135: Install occupancy sensors | $900 | $650 |
$569
13,482
kWh
|
$296
-
kW-mo/yr
|
- | - | $35 | |
| 05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $266 | $230 |
$112
2,638
kWh
|
$44
-
kW-mo/yr
|
- | - | $110 | |
| 06 | 3.5316: Contract a wood pallet recycling company | $5,558 | $350 | - | - | - |
$5,558
-
lb
|
- | |
| 07 | 3.5212: Regrind, reuse, or sell scrap plastic parts | $694 | - | - | - | - | - | $694 | |
| 08 | 4.423: Move product using mechanical means | $46,800 | $90,000 | - | - | - | - | $46,800 | |
| TOTAL RECOMMENDED | $80,766 | $105,055 |
$10,985
262,016
kWh
|
$26,480
-
kW-mo/yr
|
$5,254
-
MMBtu
|
$5,558
-
lb
|
$32,489 | ||
| TOTAL IMPLEMENTED | $6,848 | $12,650 |
$569
13,482
kWh
|
$296
-
kW-mo/yr
|
$5,254
-
MMBtu
|
- | $729 | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Solid Waste (non-haz) Savings | Administrative Changes Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs