Assessment Year | 1996 |
---|---|
Principal Product | Plastic Parts |
NAICS |
n/a
|
SIC | 3089: Plastics Products, Not Elsewhere Classified |
Sales Range | $5 M to 10M |
# of Employees | 86 |
Plant Area |
32,000
ft2
|
Annual Production | 1,500,000
lb
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Illinois |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $132,144 | 3,199,883 |
kWh
|
$0.041 |
Electricity Demand | $78,050 | 6,411 |
kW-mo/yr
|
$12.17 |
Electricity Fees | $2,197 | - |
|
- |
Natural Gas | $5,821 | 1,515 |
MMBtu
|
$3.84 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $150,805 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $145,658 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | Solid Waste (non-haz) Savings | Personnel Changes Savings | Administrative Changes Savings | Ancillary Material Cost Savings | Water Consumption Savings |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
01 | 2.3137: Use power during off-peak periods | $44,073 | $2,850 |
$30,836
793,962
kWh
|
$13,237
-
kW-mo/yr
|
- | - | - | - | - | - | - | |
02 | 2.8114: Change rate schedules or other changes in utility service | $17,093 | - | - | - | - | - | - | - | $17,093 | - | - | |
03 | 2.4133: Use most efficient type of electric motors | $11,783 | $12,980 |
$8,312
201,348
kWh
|
$3,471
-
kW-mo/yr
|
- | - | - | - | - | - | - | |
04 | 2.7111: Reduce illumination to minimum necessary levels | $5,328 | $580 |
$3,512
84,994
kWh
|
$1,418
-
kW-mo/yr
|
- | - | - | $44 | - | $354 | - | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,319 | $5,805 |
$1,975
47,773
kWh
|
$849
-
kW-mo/yr
|
- | - | - | $73 | - | $422 | - | |
06 | 2.7135: Install occupancy sensors | $2,522 | $1,125 |
$1,691
37,515
kWh
|
$831
-
kW-mo/yr
|
- | - | - | - | - | - | - | |
07 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $915 | $1,180 |
$866
21,102
kWh
|
$349
-
kW-mo/yr
|
$(-300.0)
-
MMBtu
|
- | - | - | - | - | - | |
08 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $863 | $522 |
$615
14,947
kWh
|
$248
-
kW-mo/yr
|
- | - | - | - | - | - | - | |
09 | 2.7491: Insulate glazing, walls, ceilings, and roofs | $519 | $1,515 | - | - |
$519
-
MMBtu
|
- | - | - | - | - | - | |
10 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $394 | $391 |
$251
5,275
kWh
|
$143
-
kW-mo/yr
|
- | - | - | - | - | - | - | |
11 | 3.5212: Regrind, reuse, or sell scrap plastic parts | $56,426 | $1,500 |
$(-500.0)
(-12,016)
kWh
|
- | - | - |
$4,514
-
lb
|
$(-6,225.0) | - | $58,637 | - | |
12 | 3.5315: Lease / purchase baler; sell cardboard to recycler | $6,360 | $6,750 | - | - | - | - | - | - | $6,360 | - | - | |
13 | 3.4151: Minimize water usage | $1,210 | $500 | - | - | - |
$523
-
Tgal
|
- | - | - | - |
$687
-
Tgal
|
|
TOTAL RECOMMENDED | $150,805 | $35,698 |
$47,558
1,194,900
kWh
|
$20,546
-
kW-mo/yr
|
$219
-
MMBtu
|
$523
-
Tgal
|
$4,514
-
lb
|
$(-6,108.0) | $23,453 | $59,413 |
$687
-
Tgal
|
||
TOTAL IMPLEMENTED | $145,658 | $26,807 |
$44,466
1,120,750
kWh
|
$19,205
-
kW-mo/yr
|
- |
$523
-
Tgal
|
$4,514
-
lb
|
$(-6,181.0) | $23,453 | $58,991 |
$687
-
Tgal
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | Solid Waste (non-haz) Savings | Personnel Changes Savings | Administrative Changes Savings | Ancillary Material Cost Savings | Water Consumption Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs