Assessment Year 2024
Principal Product Medical Services
NAICS 622110: General Medical and Surgical Hospitals
SIC 8062: General Medical and Surgical Hospitals
Sales Range $1
M
to 5
M
# of Employees 6,700
Plant Area 100,000
ft2
Annual Production 1
units
Production Hrs. Annual 8,760
hrs
Location (State) Arizona

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $2,228,458 38,043,420
kWh
Electricity Demand $1,307,515 92,419
kW-mo/yr
Electricity Fees $202,848 -
Natural Gas $400,652 61,753
MMBtu
Waste Disposal Costs
Water Usage $801,470 71,190
Tgal
TOTAL YEARLY COSTS $4,940,943
RECOMMENDED SAVINGS* $337,682 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* -

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Ancillary Material Cost Savings
01 2.9114: Use solar heat to make electricty $218,122 $1,758,568 $204,745
3,542,306
kWh
$47,577
-
kW-mo/yr
- $(-34,200.0)
02 2.1224: Replace boiler $56,229 $300,000 - - $56,229
-
MMBtu
-
03 2.2511: Insulate bare equipment $50,126 $154,154 $26,781
463,334
kWh
$23,345
-
kW-mo/yr
- -
04 4.611: Begin a practice of predictive / preventative maintenance $11,158 $14,100 $11,158
109,715
kWh
- - -
05 2.7132: Install timers on light switches in little used areas $1,756 $1,363 $1,756
17,259
kWh
- - -
06 2.6211: Conserve energy by efficient use of vending machines $291 $140 $264
2,595
kWh
$27
-
kW-mo/yr
- -
TOTAL RECOMMENDED $337,682 $2,228,325 $244,704
4,135,209
kWh
$70,949
-
kW-mo/yr
$56,229
-
MMBtu
$(-34,200.0)
TOTAL IMPLEMENTED - - - - - -
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Ancillary Material Cost Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs