| Assessment Year | 2024 |
|---|---|
| Principal Product | Education |
| NAICS | 611110: Elementary and Secondary Schools |
| SIC | 8211: Elementary and Secondary Schools |
| Sales Range | less than $500 k |
| # of Employees | 120 |
| Plant Area |
1,001,856
ft2
|
| Annual Production | 1
units
|
| Production Hrs. Annual | 2,550
hrs
|
| Location (State) | Arizona |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | ||
|---|---|---|---|---|---|
| Electricity Usage | $177,622 | 1,235,661 |
kWh
|
$0.14 | |
| Electricity Demand | $30,640 | 3,833 |
kW-mo/yr
|
$7.99 | |
| Electricity Fees | $26,970 | - |
|
- | |
| Natural Gas | $20,345 | 2,810 |
MMBtu
|
$7.24 | |
| Waste Disposal Costs | |||||
| Water Usage | $28,707 | 8,867 |
Tgal
|
$3.24 | |
| TOTAL YEARLY COSTS | $284,284 | ||||
| RECOMMENDED SAVINGS* | $111,504 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
| IMPLEMENTED SAVINGS* | - | ||||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Ancillary Material Cost Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.8112: Combine utility meters | $30,741 | $605 |
$28,692
-
kWh
|
$(-3,189.0)
-
kW-mo/yr
|
$5,238 | - | |
| 02 | 2.9114: Use solar heat to make electricty | $23,057 | $176,288 |
$20,787
185,595
kWh
|
$2,270
-
kW-mo/yr
|
- | - | |
| 03 | 2.9114: Use solar heat to make electricty | $17,501 | $95,089 |
$17,055
93,866
kWh
|
$446
-
kW-mo/yr
|
- | - | |
| 04 | 2.7132: Install timers on light switches in little used areas | $13,232 | $5,780 |
$13,232
94,194
kWh
|
- | - | - | |
| 05 | 2.9114: Use solar heat to make electricty | $10,418 | $95,089 |
$9,738
92,833
kWh
|
$680
-
kW-mo/yr
|
- | - | |
| 06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $7,127 | $21,892 |
$6,181
34,029
kWh
|
$791
-
kW-mo/yr
|
- | $155 | |
| 07 | 2.7144: Install spectral reflectors / delamp | $4,422 | - |
$1,909
13,655
kWh
|
$638
-
kW-mo/yr
|
- | $1,875 | |
| 08 | 2.7272: Install heat pipes / raise cooling setpoint | $3,680 | $136 |
$3,345
18,408
kWh
|
$335
-
kW-mo/yr
|
- | - | |
| 09 | 2.7135: Install occupancy sensors | $1,326 | $2,077 |
$1,132
6,438
kWh
|
$194
-
kW-mo/yr
|
- | - | |
| TOTAL RECOMMENDED | $111,504 | $396,956 |
$102,071
539,018
kWh
|
$2,165
-
kW-mo/yr
|
$5,238 | $2,030 | ||
| TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Ancillary Material Cost Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs