Assessment Year | 2024 |
---|---|
Principal Product | Office Space Rentals |
NAICS | 531120: Lessors of Nonresidential Buildings (except Miniwarehouses) |
SIC | 6512: Operators of Nonresidential Buildings |
Sales Range | $500 k to 1M |
# of Employees | 5 |
Plant Area |
14,000
ft2
|
Annual Production | 1
units
|
Production Hrs. Annual | 2,880
hrs
|
Location (State) | Arizona |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $31,934 | 278,296 |
kWh
|
$0.11 |
Electricity Demand | $10,735 | 931 |
kW-mo/yr
|
$11.53 |
Electricity Fees | $6,005 | - |
|
- |
Natural Gas | $1,238 | 56 |
MMBtu
|
$22.11 |
Other Gas | $1,181 | 32 |
MMBtu
|
$36.91 |
TOTAL YEARLY COSTS | $51,093 | |||
RECOMMENDED SAVINGS* | $23,890 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Ancillary Material Cost Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.9114: Use solar heat to make electricty | $13,353 | $72,205 |
$12,595
109,811
kWh
|
$758
-
kW-mo/yr
|
- | - | - | |
02 | 2.4322: Use or replace with energy efficient substitutes | $4,678 | $20,940 |
$3,777
32,931
kWh
|
$263
-
kW-mo/yr
|
$1,238
-
MMBtu
|
- | $(-600.0) | |
03 | 4.611: Begin a practice of predictive / preventative maintenance | $2,395 | $4,200 |
$2,395
20,881
kWh
|
- | - | - | - | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,168 | $3,380 |
$1,802
15,708
kWh
|
$226
-
kW-mo/yr
|
- | $140 | - | |
05 | 2.7135: Install occupancy sensors | $691 | $1,099 |
$614
5,357
kWh
|
$77
-
kW-mo/yr
|
- | - | - | |
06 | 2.7132: Install timers on light switches in little used areas | $425 | $200 |
$378
3,293
kWh
|
$47
-
kW-mo/yr
|
- | - | - | |
07 | 2.7423: Reduce heat gain by window tinting | $180 | $130 |
$160
1,396
kWh
|
$20
-
kW-mo/yr
|
- | - | - | |
TOTAL RECOMMENDED | $23,890 | $102,154 |
$21,721
189,377
kWh
|
$1,391
-
kW-mo/yr
|
$1,238
-
MMBtu
|
$140 | $(-600.0) | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Ancillary Material Cost Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs