Assessment Year | 2024 |
---|---|
Principal Product | Precision Power Analog Components |
NAICS | 334418: Printed Circuit Assembly (Electronic Assembly) Manufacturing |
SIC | 3674: Semiconductors and Related Devices |
Sales Range | $10 M to 50M |
# of Employees | 100 |
Plant Area |
52,800
ft2
|
Annual Production | 36,000,000
units
|
Production Hrs. Annual | 5,776
hrs
|
Location (State) | Arizona |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $122,060 | 1,689,301 |
kWh
|
$0.072 | |
Electricity Demand | $74,633 | 4,007 |
kW-mo/yr
|
$18.63 | |
Electricity Fees | $34,835 | - |
|
- | |
Natural Gas | $20,889 | 1,665 |
MMBtu
|
$12.55 | |
Waste Disposal Costs | |||||
Water Usage | $14,229 | 13,655 |
Tgal
|
$1.04 | |
TOTAL YEARLY COSTS | $266,646 | ||||
RECOMMENDED SAVINGS* | $52,751 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | $36,480 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Ancillary Material Cost Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $30,436 | $18,656 |
$16,654
230,343
kWh
|
$11,292
-
kW-mo/yr
|
- | $2,490 | - | |
02 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $9,444 | $7,395 |
$6,260
86,583
kWh
|
$3,184
-
kW-mo/yr
|
- | - | - | |
03 | 2.7135: Install occupancy sensors | $5,717 | $3,715 |
$3,599
49,771
kWh
|
$2,118
-
kW-mo/yr
|
- | - | - | |
04 | 2.1233: Analyze flue gas for proper air/fuel ratio | $3,945 | $490 | - | - |
$4,464
-
MMBtu
|
- | $(-519.0) | |
05 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $2,653 | $5,151 |
$1,759
24,333
kWh
|
$894
-
kW-mo/yr
|
- | - | - | |
06 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $327 | $146 |
$217
3,004
kWh
|
$110
-
kW-mo/yr
|
- | - | - | |
07 | 2.6211: Conserve energy by efficient use of vending machines | $229 | $86 |
$153
2,114
kWh
|
$76
-
kW-mo/yr
|
- | - | - | |
TOTAL RECOMMENDED | $52,751 | $35,639 |
$28,642
396,148
kWh
|
$17,674
-
kW-mo/yr
|
$4,464
-
MMBtu
|
$2,490 | $(-519.0) | ||
TOTAL IMPLEMENTED | $36,480 | $22,517 |
$20,470
283,118
kWh
|
$13,520
-
kW-mo/yr
|
- | $2,490 | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Ancillary Material Cost Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs