Assessment Year | 2021 |
---|---|
Principal Product | Treated Wastewater |
NAICS | 221320: Sewage Treatment Facilities |
SIC | 4952: Sewerage Systems |
Sales Range | less than $500 k |
# of Employees | 13 |
Plant Area |
40,000
ft2
|
Annual Production | 654,000
Tgal
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Arizona |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $196,689 | 2,787,087 |
kWh
|
$0.071 |
Electricity Demand | $63,432 | 6,170 |
kW-mo/yr
|
$10.28 |
Electricity Fees | $23,511 | - |
|
- |
TOTAL YEARLY COSTS | $283,632 | |||
RECOMMENDED SAVINGS* | $47,148 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $47,148 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|
01 | 2.8112: Combine utility meters | $21,443 | $1,473 |
$62,685
-
kWh
|
$(-42,007.0)
-
kW-mo/yr
|
$765 | |
02 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $13,179 | $8,066 |
$10,687
150,514
kWh
|
$2,492
-
kW-mo/yr
|
- | |
03 | 2.4323: Use optimum size and capacity equipment | $9,788 | $3,941 |
$8,452
119,048
kWh
|
$1,336
-
kW-mo/yr
|
- | |
04 | 2.6125: Keep equipment clean | $1,693 | $2,174 |
$1,693
23,848
kWh
|
- | - | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,045 | $2,451 |
$894
12,589
kWh
|
$172
-
kW-mo/yr
|
$(-21.0) | |
TOTAL RECOMMENDED | $47,148 | $18,105 |
$84,411
305,999
kWh
|
$(-38,007.0)
-
kW-mo/yr
|
$744 | ||
TOTAL IMPLEMENTED | $47,148 | $18,105 |
$84,411
305,999
kWh
|
$(-38,007.0)
-
kW-mo/yr
|
$744 |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs