Assessment Year 2020
Principal Product Treated Surface Water
NAICS 221310: Water Supply and Irrigation Systems
SIC 4941: Water Supply
Sales Range less than $500
k
# of Employees 50
Plant Area 76,000
ft2
Annual Production 2,900,000
Tgal
Production Hrs. Annual 7,320
hrs
Location (State) Arizona

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $433,417 7,194,567
kWh
Electricity Demand $237,609 18,514
kW-mo/yr
Electricity Fees $53,943 -
TOTAL YEARLY COSTS $724,969
RECOMMENDED SAVINGS* $25,517 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $8,102

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Administrative Changes Savings
01 2.3137: Use power during off-peak periods $7,396 $298 - - $7,396
02 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $7,249 $1,100 $5,671
94,516
kWh
$1,578
-
kW-mo/yr
-
03 2.7142: Utilize higher efficiency lamps and/or ballasts $5,880 $2,996 $4,592
76,538
kWh
$1,288
-
kW-mo/yr
-
04 2.2622: Replace existing chiller with high efficiency model $3,159 $9,000 $2,466
41,104
kWh
$693
-
kW-mo/yr
-
05 2.7135: Install occupancy sensors $1,068 $540 $1,068
17,828
kWh
- -
06 2.4322: Use or replace with energy efficient substitutes $706 $912 $553
9,232
kWh
$153
-
kW-mo/yr
-
07 2.6211: Conserve energy by efficient use of vending machines $59 $113 $46
769
kWh
$13
-
kW-mo/yr
-
TOTAL RECOMMENDED $25,517 $14,959 $14,396
239,987
kWh
$3,725
-
kW-mo/yr
$7,396
TOTAL IMPLEMENTED $8,102 $1,210 $553
9,232
kWh
$153
-
kW-mo/yr
$7,396
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Administrative Changes Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs