Assessment Year | 2006 |
---|---|
Principal Product | Boric acid, lime, cement and stucco |
NAICS | 325180: Other Basic Inorganic Chemical Manufacturing |
SIC | 2819: Industrial Inorganic Chemicals, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 50 |
Plant Area |
53,000
ft2
|
Annual Production | 0
units
|
Production Hrs. Annual | 6,096
hrs
|
Location (State) | Arizona |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $64,408 | 685,129 |
kWh
|
$0.094 |
Electricity Demand | $2,258 | 2,522 |
kW-mo/yr
|
$0.90 |
Natural Gas | $15,491 | 1,383 |
MMBtu
|
$11.20 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $65,733 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Increase in Production Savings |
---|---|---|---|---|---|---|---|
01 | 4.652: Replace existing equipment with more suitable substitutes | $53,975 | $63,819 | - | - | $53,975 | |
02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $3,093 | $1,000 |
$2,973
31,632
kWh
|
$120
-
kW-mo/yr
|
- | |
03 | 2.7232: Replace existing hvac unit with high efficiency model | $2,465 | $10,000 |
$2,369
25,211
kWh
|
$96
-
kW-mo/yr
|
- | |
04 | 2.4133: Use most efficient type of electric motors | $2,236 | $20,867 |
$2,149
23,149
kWh
|
$87
-
kW-mo/yr
|
- | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,551 | $2,513 |
$1,491
15,517
kWh
|
$60
-
kW-mo/yr
|
- | |
06 | 2.4323: Use optimum size and capacity equipment | $933 | $8,000 |
$897
9,544
kWh
|
$36
-
kW-mo/yr
|
- | |
07 | 2.9112: Use solar heat to heat water | $904 | $6,400 |
$869
9,602
kWh
|
$35
-
kW-mo/yr
|
- | |
08 | 2.9114: Use solar heat to make electricty | $576 | $22,500 |
$576
9,000
kWh
|
- | - | |
TOTAL RECOMMENDED | $65,733 | $135,099 |
$11,324
123,655
kWh
|
$434
-
kW-mo/yr
|
$53,975 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Increase in Production Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs