Assessment Year | 2004 |
---|---|
Principal Product | Newspapers |
NAICS | 511110: Newspaper Publishers |
SIC | 2711: Newspapers: Publishing, or Publishing and Printing |
Sales Range | $50 M to 100M |
# of Employees | 500 |
Plant Area |
100,000
ft2
|
Annual Production | 12,000
ton
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Arizona |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $248,490 | 4,939,049 |
kWh
|
$0.050 |
Electricity Demand | $41,290 | 11,986 |
kW-mo/yr
|
$3.44 |
Electricity Fees | $23,438 | - |
|
- |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $25,499 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $5,155 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $4,518 | $500 |
$4,116
75,966
kWh
|
$402
-
kW-mo/yr
|
|
02 | 2.6218: Turn off equipment when not in use | $1,736 | $60 |
$830
20,250
kWh
|
$906
-
kW-mo/yr
|
|
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,601 | $14,813 | n/a |
$4,192
77,368
kWh
|
$409
-
kW-mo/yr
|
04 | 2.7135: Install occupancy sensors | $309 | $675 |
$309
5,694
kWh
|
- | |
05 | 2.4133: Use most efficient type of electric motors | $2,451 | $2,911 |
$2,228
42,225
kWh
|
$223
-
kW-mo/yr
|
|
06 | 2.7232: Replace existing hvac unit with high efficiency model | $9,180 | $10,083 | n/a |
$8,619
159,082
kWh
|
$561
-
kW-mo/yr
|
07 | 2.4231: Reduce the pressure of compressed air to the minimum required | $2,704 | $60 |
$2,464
45,493
kWh
|
$240
-
kW-mo/yr
|
|
TOTAL RECOMMENDED | $25,499 | $29,102 |
$22,758
426,078
kWh
|
$2,741
-
kW-mo/yr
|
||
TOTAL IMPLEMENTED | $5,155 | $2,971 |
$4,692
87,718
kWh
|
$463
-
kW-mo/yr
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs