Assessment Year | 2004 |
---|---|
Principal Product | Fluid milk and milk products |
NAICS | 311511: Fluid Milk Manufacturing |
SIC | 2026: Fluid Milk |
Sales Range | $50 M to 100M |
# of Employees | 220 |
Plant Area |
457,380
ft2
|
Annual Production | 7,500
Tgal
|
Production Hrs. Annual | 5,408
hrs
|
Location (State) | Nevada |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $661,489 | 9,142,207 |
kWh
|
$0.072 |
Electricity Demand | $51,439 | 18,818 |
kW-mo/yr
|
$2.73 |
Electricity Fees | $93,711 | - |
|
- |
Natural Gas | $368,097 | 84,417 |
MMBtu
|
$4.36 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $109,590 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $105,262 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Other Liquid (non-haz) Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.4134: Replace electric motor with fossil fuel engine | $84,336 | $312,400 |
$139,481
1,658,472
kWh
|
$11,689
-
kW-mo/yr
|
$(-66,834.0)
-
MMBtu
|
- | - | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $9,343 | $30 |
$8,623
113,466
kWh
|
$720
-
kW-mo/yr
|
- | - | - | |
03 | 3.5112: Reprocess spent oils on site for re-use | $6,189 | $11,970 |
$(-104.0)
(-1,365)
kWh
|
$(-34.0)
-
kW-mo/yr
|
$6,027
-
MMBtu
|
$300
-
gal
|
- | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,340 | $7,360 |
$2,001
26,326
kWh
|
$168
-
kW-mo/yr
|
- | - | $171 | |
05 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,986 | $20 |
$1,832
24,105
kWh
|
$154
-
kW-mo/yr
|
- | - | - | |
06 | 2.4133: Use most efficient type of electric motors | $1,843 | $1,418 |
$1,718
22,606
kWh
|
$125
-
kW-mo/yr
|
- | - | - | |
07 | 2.2414: Use waste heat from hot flue gases to preheat | $1,783 | $1,320 | - | - |
$1,783
-
MMBtu
|
- | - | |
08 | 2.2135: Repair and eliminate steam leaks | $1,211 | $150 | - | - |
$1,211
-
MMBtu
|
- | - | |
09 | 2.7232: Replace existing hvac unit with high efficiency model | $559 | $2,178 |
$499
6,571
kWh
|
$60
-
kW-mo/yr
|
- | - | - | |
TOTAL RECOMMENDED | $109,590 | $336,846 |
$154,050
1,850,181
kWh
|
$12,882
-
kW-mo/yr
|
$(-57,813.0)
-
MMBtu
|
$300
-
gal
|
$171 | ||
TOTAL IMPLEMENTED | $105,262 | $333,328 |
$151,719
1,819,505
kWh
|
$12,668
-
kW-mo/yr
|
$(-59,596.0)
-
MMBtu
|
$300
-
gal
|
$171 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Other Liquid (non-haz) Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs