| Assessment Year | 2004 |
|---|---|
| Principal Product | Aircraft Parts and Auxiliary Equipment |
| NAICS | 336413: Other Aircraft Parts and Auxiliary Equipment Manufacturing |
| SIC | 3728: Aircraft Parts and Auxiliary Equipment, Not Elsewhere Classified |
| Sales Range | $10 M to 50M |
| # of Employees | 90 |
| Plant Area |
34,100
ft2
|
| Annual Production | 40,000
pieces
|
| Production Hrs. Annual | 4,042
hrs
|
| Location (State) | Arizona |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $95,123 | 1,152,319 |
kWh
|
$0.083 |
| Electricity Demand | $7,821 | 4,831 |
kW-mo/yr
|
$1.62 |
| Electricity Fees | $6,581 | - |
|
- |
| Natural Gas | $19,385 | 2,378 |
MMBtu
|
$8.15 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $16,917 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $1,768 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
|---|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $6,472 | $11,485 |
$2,319
32,036
kWh
|
$4,153
-
kW-mo/yr
|
|
| 02 | 2.7135: Install occupancy sensors | $880 | $900 |
$880
12,150
kWh
|
- | |
| 03 | 2.7232: Replace existing hvac unit with high efficiency model | $7,797 | $26,415 |
$6,847
94,583
kWh
|
$950
-
kW-mo/yr
|
|
| 04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $468 | $737 |
$468
6,466
kWh
|
- | |
| 05 | 2.4231: Reduce the pressure of compressed air to the minimum required | $168 | $60 |
$139
1,923
kWh
|
$29
-
kW-mo/yr
|
|
| 06 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,132 | $30 |
$937
12,943
kWh
|
$195
-
kW-mo/yr
|
|
| TOTAL RECOMMENDED | $16,917 | $39,627 |
$11,590
160,101
kWh
|
$5,327
-
kW-mo/yr
|
||
| TOTAL IMPLEMENTED | $1,768 | $827 |
$1,544
21,332
kWh
|
$224
-
kW-mo/yr
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs