Assessment Year | 2003 |
---|---|
Principal Product | Wood Fuel Pellets |
NAICS | 321999: All Other Miscellaneous Wood Product Manufacturing |
SIC | 2499: Wood Products, Not Elsewhere Classified |
Sales Range | $1 M to 5M |
# of Employees | 32 |
Plant Area |
958,320
ft2
|
Annual Production | 35,000
ton
|
Production Hrs. Annual | 7,704
hrs
|
Location (State) | Arizona |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $243,095 | 4,274,000 |
kWh
|
$0.057 |
Electricity Demand | $14,581 | 8,944 |
kW-mo/yr
|
$1.63 |
Electricity Fees | $16,610 | - |
|
- |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $100,160 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $8,682 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Solid Waste (non-haz) Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.4133: Use most efficient type of electric motors | $790 | $1,643 |
$680
14,903
kWh
|
$110
-
kW-mo/yr
|
- | - | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $290 | $1,535 |
$176
3,866
kWh
|
$95
-
kW-mo/yr
|
- | $19 | |
03 | 2.7135: Install occupancy sensors | $140 | $450 |
$140
3,074
kWh
|
- | - | - | |
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $7,328 | $60 |
$5,783
126,826
kWh
|
$1,545
-
kW-mo/yr
|
- | - | |
05 | 2.4231: Reduce the pressure of compressed air to the minimum required | $183 | $30 |
$144
3,159
kWh
|
$39
-
kW-mo/yr
|
- | - | |
06 | 2.7232: Replace existing hvac unit with high efficiency model | $274 | $350 |
$167
3,657
kWh
|
$107
-
kW-mo/yr
|
- | - | |
07 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $88,723 | $78,120 |
$78,541
1,740,885
kWh
|
$10,182
-
kW-mo/yr
|
- | - | |
08 | 3.5311: Recover and reuse waste material | $2,432 | $1,059 | n/a | - | - |
$2,432
-
lb
|
- |
TOTAL RECOMMENDED | $100,160 | $83,247 |
$85,631
1,896,370
kWh
|
$12,078
-
kW-mo/yr
|
$2,432
-
lb
|
$19 | ||
TOTAL IMPLEMENTED | $8,682 | $3,588 |
$6,806
149,252
kWh
|
$1,857
-
kW-mo/yr
|
- | $19 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Solid Waste (non-haz) Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs