Assessment Year | 2003 |
---|---|
Principal Product | Wallboard, Plaster |
NAICS | 327420: Gypsum Product Manufacturing |
SIC | 3275: Gypsum Products |
Sales Range | $50 M to 100M |
# of Employees | 110 |
Plant Area |
600,000
ft2
|
Annual Production | 218,124
thousand feet
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Nevada |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $1,976,152 | 31,300,918 |
kWh
|
$0.063 |
Electricity Demand | $169,642 | 72,871 |
kW-mo/yr
|
$2.33 |
Electricity Fees | $535,231 | - |
|
- |
Natural Gas | $9,390,449 | 2,475,345 |
MMBtu
|
$3.79 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $1,075,962 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $6,985 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.7145: Install skylights | $552 | $22,526 |
$552
195,216
kWh
|
- | - | |
02 | 2.4133: Use most efficient type of electric motors | $265 | $2,353 |
$141
18,757
kWh
|
$124
-
kW-mo/yr
|
- | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,751 | $10,939 |
$900
52,201
kWh
|
$851
-
kW-mo/yr
|
- | |
04 | 2.7135: Install occupancy sensors | $6,720 | $750 |
$6,720
6,026
kWh
|
- | - | |
05 | 2.7232: Replace existing hvac unit with high efficiency model | $17,401 | $10,050 |
$16,801
141,391
kWh
|
$600
-
kW-mo/yr
|
- | |
06 | 2.3415: Use a fossil fuel engine to cogenerate electricity or motive power; and utilize heat | $1,049,273 | $2,100,000 |
$1,555,500
25,500,000
kWh
|
$255,367
-
kW-mo/yr
|
$(-761,594.0)
-
MMBtu
|
|
TOTAL RECOMMENDED | $1,075,962 | $2,146,618 |
$1,580,614
25,913,591
kWh
|
$256,942
-
kW-mo/yr
|
$(-761,594.0)
-
MMBtu
|
||
TOTAL IMPLEMENTED | $6,985 | $3,103 |
$6,861
24,783
kWh
|
$124
-
kW-mo/yr
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs