| Assessment Year | 2002 |
|---|---|
| Principal Product | Bee Pollen Products |
| NAICS |
n/a
|
| SIC | 2032: Canned Specialties |
| Sales Range | $10 M to 50M |
| # of Employees | 45 |
| Plant Area |
43,000
ft2
|
| Annual Production | 2,500,000
pieces
|
| Production Hrs. Annual | 2,151
hrs
|
| Location (State) | Arizona |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $21,921 | 679,734 |
kWh
|
$0.032 |
| Electricity Demand | $9,635 | 5,603 |
kW-mo/yr
|
$1.72 |
| Electricity Fees | $12,290 | - |
|
- |
| Natural Gas | $1,270 | 104 |
MMBtu
|
$12.21 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $28,089 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Solid Waste (non-haz) Savings | Personnel Changes Savings | Administrative Changes Savings | Ancillary Material Cost Savings |
|---|---|---|---|---|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,018 | $3,240 |
$596
12,260
kWh
|
$350
-
kW-mo/yr
|
- | - | - | $72 | |
| 02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $948 | $3,673 |
$666
13,659
kWh
|
$282
-
kW-mo/yr
|
- | - | - | - | |
| 03 | 2.7145: Install skylights | $1,360 | $5,352 |
$1,360
27,982
kWh
|
- | - | - | - | - | |
| 04 | 2.7135: Install occupancy sensors | $230 | $975 |
$164
3,358
kWh
|
$66
-
kW-mo/yr
|
- | - | - | - | |
| 05 | 2.4231: Reduce the pressure of compressed air to the minimum required | $256 | $60 |
$139
2,862
kWh
|
$117
-
kW-mo/yr
|
- | - | - | - | |
| 06 | 3.5217: Reuse / recycle/ sell paper products | $832 | $60 | - | - |
$832
-
lb
|
- | - | - | |
| 07 | 4.123: Reduce defects by reducing product tipping | $259 | $65 |
$92
1,894
kWh
|
$59
-
kW-mo/yr
|
- | $108 | - | - | |
| 08 | 4.513: Re-arrange equipment layout to reduce labor costs | $23,186 | $8,988 | - | - | - | - | $23,186 | - | |
| TOTAL RECOMMENDED | $28,089 | $22,413 |
$3,017
62,015
kWh
|
$874
-
kW-mo/yr
|
$832
-
lb
|
$108 | $23,186 | $72 | ||
| TOTAL IMPLEMENTED | - | - | - | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Solid Waste (non-haz) Savings | Personnel Changes Savings | Administrative Changes Savings | Ancillary Material Cost Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs