Assessment Year 2000
Principal Product Dispersion Systems, Extended Range Munitions, Gas Generators
NAICS
n/a
SIC 3483: Ammunition, Except for Small Arms
Sales Range $10
M
to 50
M
# of Employees 155
Plant Area 500,000
ft2
Annual Production 250,000
pieces
Production Hrs. Annual 2,588
hrs
Location (State) Arizona

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $283,570 4,997,655
kWh
Electricity Demand $31,099 11,295
kW-mo/yr
Electricity Fees $20,000 -
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $81,073 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $34,324

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Personnel Changes Savings Administrative Changes Savings Ancillary Material Cost Savings By-product Production Savings
01 2.7142: Utilize higher efficiency lamps and/or ballasts $8,756 $17,407 $4,118
105,803
kWh
$4,638
-
kW-mo/yr
- - - -
02 2.7142: Utilize higher efficiency lamps and/or ballasts $682 $315 $198
4,982
kWh
$212
-
kW-mo/yr
$233 - $39 -
03 2.7133: Use separate switches on perimeter lighting which may be turned off when natural light is available $501 $240 $501
12,896
kWh
- - - - -
04 2.7135: Install occupancy sensors $4,295 $4,875 $2,507
64,478
kWh
$1,788
-
kW-mo/yr
- - - -
05 2.4133: Use most efficient type of electric motors $572 $2,394 $247
6,448
kWh
$325
-
kW-mo/yr
- - - -
06 2.7232: Replace existing hvac unit with high efficiency model $25,067 $24,000 $14,713
378,370
kWh
$10,354
-
kW-mo/yr
- - - -
07 3.6192: Use a less expensive method of waste removal $668 $120 - - - $668 - -
08 3.5316: Contract a wood pallet recycling company $2,700 $60 - - - - - $2,700
09 4.212: Adopt in-house material generation $37,832 $100,000 - - - - - $37,832
TOTAL RECOMMENDED $81,073 $149,411 $22,284
572,977
kWh
$17,317
-
kW-mo/yr
$233 $668 $39 $40,532
TOTAL IMPLEMENTED $34,324 $41,647 $19,332
497,069
kWh
$14,992
-
kW-mo/yr
- - - -
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Personnel Changes Savings Administrative Changes Savings Ancillary Material Cost Savings By-product Production Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs