Assessment Year | 2000 |
---|---|
Principal Product | Wood and Laminated Office and Store Fixtures |
NAICS |
n/a
|
SIC | 2431: Millwork |
Sales Range | $5 M to 10M |
# of Employees | 86 |
Plant Area |
91,000
ft2
|
Annual Production | 2,500,000
lb
|
Production Hrs. Annual | 2,431
hrs
|
Location (State) | Arizona |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $58,471 | 943,728 |
kWh
|
$0.062 |
Electricity Demand | $9,409 | 3,606 |
kW-mo/yr
|
$2.61 |
Electricity Fees | $6,280 | - |
|
- |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $30,928 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $17,320 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Solid Waste (non-haz) Savings | Personnel Changes Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,064 | $2,486 |
$719
12,896
kWh
|
$345
-
kW-mo/yr
|
- | - | - | |
02 | 2.7121: Utilize daylight whenever possible in lieu of artificial light | $1,003 | $800 |
$1,003
17,878
kWh
|
- | - | - | - | |
03 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $10,564 | $3,800 |
$6,987
123,974
kWh
|
$3,577
-
kW-mo/yr
|
- | - | - | |
04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,270 | $60 |
$1,270
22,567
kWh
|
- | - | - | - | |
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $809 | $100 |
$535
9,379
kWh
|
$274
-
kW-mo/yr
|
- | - | - | |
06 | 3.6192: Use a less expensive method of waste removal | $852 | $60 | - | - | - | - | $852 | |
07 | 3.5217: Reuse / recycle/ sell paper products | $315 | $60 | - | - |
$315
-
lb
|
- | - | |
08 | 4.821: Pay bills on time to avoid late fees | $771 | $60 | - | - | - | - | $771 | |
09 | 4.432: Cross-train personnel to avoid lost time | $14,280 | $2,240 | - | - | - | $14,280 | - | |
TOTAL RECOMMENDED | $30,928 | $9,666 |
$10,514
186,694
kWh
|
$4,196
-
kW-mo/yr
|
$315
-
lb
|
$14,280 | $1,623 | ||
TOTAL IMPLEMENTED | $17,320 | $4,946 |
$1,254
22,275
kWh
|
$619
-
kW-mo/yr
|
$315
-
lb
|
$14,280 | $852 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Solid Waste (non-haz) Savings | Personnel Changes Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs