Assessment Year | 1997 |
---|---|
Principal Product | Processed Meats |
NAICS |
n/a
|
SIC | 2013: Sausages and Other Prepared Meat Products |
Sales Range | $10 M to 50M |
# of Employees | 100 |
Plant Area |
15,000
ft2
|
Annual Production | 40,800,000
lb
|
Production Hrs. Annual | 4,208
hrs
|
Location (State) | Arizona |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $76,804 | 1,398,886 |
kWh
|
$0.055 |
Electricity Demand | $39,782 | 3,461 |
kW-mo/yr
|
$11.49 |
Electricity Fees | $11,531 | - |
|
- |
Natural Gas | $15,866 | 3,644 |
MMBtu
|
$4.35 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $23,880 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $11,595 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | Administrative Changes Savings | By-product Production Savings |
---|---|---|---|---|---|---|---|---|---|---|
01 | 2.6218: Turn off equipment when not in use | $1,135 | - |
$1,135
12,016
kWh
|
- | - | - | - | - | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,489 | $120 |
$1,538
25,498
kWh
|
$951
-
kW-mo/yr
|
- | - | - | - | |
03 | 2.4133: Use most efficient type of electric motors | $3,559 | $3,945 |
$1,461
26,084
kWh
|
$2,098
-
kW-mo/yr
|
- | - | - | - | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,068 | $2,154 |
$681
12,309
kWh
|
$387
-
kW-mo/yr
|
- | - | - | - | |
05 | 2.7135: Install occupancy sensors | $885 | $675 |
$885
8,792
kWh
|
- | - | - | - | - | |
06 | 3.4154: Eliminate leaks in water lines and valves | $73 | $194 | - | - |
$51
-
MMBtu
|
$22
-
Tgal
|
- | - | |
07 | 3.4151: Minimize water usage | $422 | - | - | - | - |
$422
-
Tgal
|
- | - | |
08 | 4.811: Demolish old building to reduce tax and insurance bills | $4,589 | $1,300 | - | - | - | - | $4,589 | - | |
09 | 4.521: Clear and rent existing space | $9,660 | $10,000 | - | - | - | - | - | $9,660 | |
TOTAL RECOMMENDED | $23,880 | $18,388 |
$5,700
84,699
kWh
|
$3,436
-
kW-mo/yr
|
$51
-
MMBtu
|
$444
-
Tgal
|
$4,589 | $9,660 | ||
TOTAL IMPLEMENTED | $11,595 | $6,234 |
$3,884
60,374
kWh
|
$3,049
-
kW-mo/yr
|
$51
-
MMBtu
|
$22
-
Tgal
|
$4,589 | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | Administrative Changes Savings | By-product Production Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs