| Assessment Year | 1996 |
|---|---|
| Principal Product | Brass Door Locks |
| NAICS |
n/a
|
| SIC | 3429: Hardware, Not Elsewhere Classified |
| Sales Range | $100 M to 500M |
| # of Employees | 475 |
| Plant Area |
238,000
ft2
|
| Annual Production | 9,000,000
pieces
|
| Production Hrs. Annual | 5,700
hrs
|
| Location (State) | Arizona |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $779,895 | 11,136,284 |
kWh
|
$0.070 |
| Electricity Demand | $173,102 | 22,860 |
kW-mo/yr
|
$7.57 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $112,753 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $108,849 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Water Disposal Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.2622: Replace existing chiller with high efficiency model | $34,527 | $45,000 |
$26,214
374,560
kWh
|
$11,582
-
kW-mo/yr
|
$(-3,269.0)
-
Tgal
|
|
| 02 | 2.7232: Replace existing hvac unit with high efficiency model | $5,963 | $7,000 |
$3,196
58,910
kWh
|
$2,767
-
kW-mo/yr
|
- | |
| 03 | 2.4133: Use most efficient type of electric motors | $24,827 | $17,598 |
$20,143
287,808
kWh
|
$4,684
-
kW-mo/yr
|
- | |
| 04 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $8,838 | - |
$7,239
103,458
kWh
|
$1,599
-
kW-mo/yr
|
- | |
| 05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $9,599 | $25,001 |
$9,365
111,958
kWh
|
$234
-
kW-mo/yr
|
- | |
| 06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,904 | $6,140 |
$3,198
45,721
kWh
|
$706
-
kW-mo/yr
|
- | |
| 07 | 2.7135: Install occupancy sensors | $881 | $450 |
$881
12,603
kWh
|
- | - | |
| 08 | 3.1222: Reduce water use with counter current rinsing | $24,214 | $900 | - | - |
$24,214
-
Tgal
|
|
| TOTAL RECOMMENDED | $112,753 | $102,089 |
$70,236
995,018
kWh
|
$21,572
-
kW-mo/yr
|
$20,945
-
Tgal
|
||
| TOTAL IMPLEMENTED | $108,849 | $95,949 |
$67,038
949,297
kWh
|
$20,866
-
kW-mo/yr
|
$20,945
-
Tgal
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Water Disposal Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs