Assessment Year | 1996 |
---|---|
Principal Product | Bread |
NAICS |
n/a
|
SIC | 2051: Bread and Other Bakery Products, Except Cookies and Crackers |
Sales Range | $10 M to 50M |
# of Employees | 150 |
Plant Area |
120,000
ft2
|
Annual Production | 14,000,000
lb
|
Production Hrs. Annual | 4,590
hrs
|
Location (State) | Arizona |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $145,340 | 2,226,846 |
kWh
|
$0.065 |
Electricity Demand | $36,938 | 4,972 |
kW-mo/yr
|
$7.43 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $13,371 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $10,863 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Solid Waste (non-haz) Savings |
---|---|---|---|---|---|---|---|
01 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,866 | - |
$1,866
29,015
kWh
|
- | - | |
02 | 2.4235: Remove or close off unneeded compressed air lines | $1,309 | $255 |
$845
13,189
kWh
|
$464
-
kW-mo/yr
|
- | |
03 | 2.4235: Remove or close off unneeded compressed air lines | $416 | $120 |
$175
2,638
kWh
|
$241
-
kW-mo/yr
|
- | |
04 | 2.4239: Eliminate or reduce compressed air usage | $882 | $100 |
$657
10,258
kWh
|
$225
-
kW-mo/yr
|
- | |
05 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $2,378 | $1,938 |
$1,866
29,015
kWh
|
$512
-
kW-mo/yr
|
- | |
06 | 2.7232: Replace existing hvac unit with high efficiency model | $688 | $1,400 |
$429
7,913
kWh
|
$259
-
kW-mo/yr
|
- | |
07 | 2.7135: Install occupancy sensors | $1,230 | $1,050 |
$1,230
19,343
kWh
|
- | - | |
08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $103 | $128 |
$80
1,172
kWh
|
$23
-
kW-mo/yr
|
- | |
09 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $590 | $1,236 |
$415
6,448
kWh
|
$175
-
kW-mo/yr
|
- | |
10 | 3.7121: Improve handling practices | $3,909 | $1,500 | - | - |
$3,909
-
lb
|
|
TOTAL RECOMMENDED | $13,371 | $7,727 |
$7,563
118,991
kWh
|
$1,899
-
kW-mo/yr
|
$3,909
-
lb
|
||
TOTAL IMPLEMENTED | $10,863 | $4,041 |
$5,489
85,287
kWh
|
$1,465
-
kW-mo/yr
|
$3,909
-
lb
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Solid Waste (non-haz) Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs