| Assessment Year | 1996 |
|---|---|
| Principal Product | Custom Semiconductors |
| NAICS |
n/a
|
| SIC | 3674: Semiconductors and Related Devices |
| Sales Range | $10 M to 50M |
| # of Employees | 550 |
| Plant Area |
146,735
ft2
|
| Annual Production | 35,000
pieces
|
| Production Hrs. Annual | 8,400
hrs
|
| Location (State) | Arizona |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $983,135 | 24,217,468 |
kWh
|
$0.041 |
| Electricity Demand | $395,316 | 36,835 |
kW-mo/yr
|
$10.73 |
| Natural Gas | $197,959 | 51,371 |
MMBtu
|
$3.85 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $117,351 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $89,441 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | Ancillary Material Cost Savings |
|---|---|---|---|---|---|---|---|---|---|
| 01 | 2.7232: Replace existing hvac unit with high efficiency model | $9,415 | $7,000 |
$4,210
113,716
kWh
|
$5,205
-
kW-mo/yr
|
- | - | - | |
| 02 | 2.7232: Replace existing hvac unit with high efficiency model | $4,108 | $1,750 |
$3,457
53,048
kWh
|
$651
-
kW-mo/yr
|
- | - | - | |
| 03 | 2.7261: Install timers and/or thermostats | $1,233 | $2,880 |
$1,233
19,050
kWh
|
- | - | - | - | |
| 04 | 2.2622: Replace existing chiller with high efficiency model | $21,398 | $25,000 |
$13,965
371,336
kWh
|
$7,433
-
kW-mo/yr
|
- | - | - | |
| 05 | 2.2622: Replace existing chiller with high efficiency model | $15,892 | $35,000 |
$10,700
255,276
kWh
|
$5,192
-
kW-mo/yr
|
- | - | - | |
| 06 | 2.7241: Install outside air damper / economizer on hvac unit | $10,968 | $6,000 |
$10,968
283,705
kWh
|
- | - | - | - | |
| 07 | 2.7241: Install outside air damper / economizer on hvac unit | $2,569 | $1,500 |
$2,569
39,566
kWh
|
- | - | - | - | |
| 08 | 2.4133: Use most efficient type of electric motors | $5,954 | $4,163 |
$3,944
104,924
kWh
|
$2,010
-
kW-mo/yr
|
- | - | - | |
| 09 | 2.4231: Reduce the pressure of compressed air to the minimum required | $315 | - |
$315
8,499
kWh
|
- | - | - | - | |
| 10 | 2.7111: Reduce illumination to minimum necessary levels | $3,519 | $2,240 |
$2,405
90,563
kWh
|
$1,114
-
kW-mo/yr
|
- | - | - | |
| 11 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $27,847 | $54,958 |
$20,408
544,256
kWh
|
$7,439
-
kW-mo/yr
|
- | - | - | |
| 12 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $207 | $800 |
$153
3,517
kWh
|
$54
-
kW-mo/yr
|
- | - | - | |
| 13 | 2.7135: Install occupancy sensors | $3,057 | $2,475 |
$3,057
75,615
kWh
|
- | - | - | - | |
| 14 | 2.1233: Analyze flue gas for proper air/fuel ratio | $4,827 | $1,200 | - | - |
$4,827
-
MMBtu
|
- | - | |
| 15 | 3.4113: Treat and reuse rinse waters | $6,042 | $22,500 | - | - | - |
$11,542
-
Tgal
|
$(-5,500.0) | |
| TOTAL RECOMMENDED | $117,351 | $167,466 |
$77,384
1,963,071
kWh
|
$29,098
-
kW-mo/yr
|
$4,827
-
MMBtu
|
$11,542
-
Tgal
|
$(-5,500.0) | ||
| TOTAL IMPLEMENTED | $89,441 | $129,071 |
$56,684
1,442,556
kWh
|
$27,930
-
kW-mo/yr
|
$4,827
-
MMBtu
|
- | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | Ancillary Material Cost Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs