| Assessment Year | 1995 |
|---|---|
| Principal Product | Turbine Engine Components |
| NAICS |
n/a
|
| SIC | 3724: Aircraft Engines and Engine Parts |
| Sales Range | $10 M to 50M |
| # of Employees | 130 |
| Plant Area |
45,000
ft2
|
| Annual Production | 500,000
pieces
|
| Production Hrs. Annual | 7,488
hrs
|
| Location (State) | Arizona |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $251,883 | 3,719,519 |
kWh
|
$0.068 |
| Natural Gas | $13,675 | 2,313 |
MMBtu
|
$5.91 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $70,587 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|
| 01 | 2.4133: Use most efficient type of electric motors | $17,480 | $12,523 |
$17,480
267,585
kWh
|
- | |
| 02 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $5,251 | - |
$5,251
80,891
kWh
|
- | |
| 03 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $618 | $1,210 |
$618
9,379
kWh
|
- | |
| 04 | 2.2437: Recover waste heat from equipment | $3,078 | $1,000 | - |
$3,078
-
MMBtu
|
|
| 05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $11,309 | $1,200 |
$11,309
180,246
kWh
|
- | |
| 06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $12,535 | $18,701 |
$12,535
195,193
kWh
|
- | |
| 07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $432 | $656 |
$432
7,034
kWh
|
- | |
| 08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $389 | $600 |
$389
6,448
kWh
|
- | |
| 09 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $1,722 | $1,360 |
$2,346
34,584
kWh
|
$(-624.0)
-
MMBtu
|
|
| 10 | 2.7232: Replace existing hvac unit with high efficiency model | $17,773 | $54,725 |
$17,773
243,845
kWh
|
- | |
| TOTAL RECOMMENDED | $70,587 | $91,975 |
$68,133
1,025,205
kWh
|
$2,454
-
MMBtu
|
||
| TOTAL IMPLEMENTED | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs