Assessment Year | 1992 |
---|---|
Principal Product | PLASTIC INJECTION MOLDS |
NAICS |
n/a
|
SIC | 3089: Plastics Products, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 130 |
Plant Area |
n/a
|
Annual Production | 143,612
pieces
|
Production Hrs. Annual | 8,736
hrs
|
Location (State) | Arizona |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $453,088 | 7,586,460 |
kWh
|
$0.060 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $55,070 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $55,070 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|
01 | 2.4133: Use most efficient type of electric motors | $1,226 | $5,173 |
$1,226
20,516
kWh
|
- | |
02 | 2.7312: Minimize use of outside make-up air for ventilation except when used for economizer cycle | $11,610 | $9,350 |
$11,610
194,607
kWh
|
- | |
03 | 2.7422: Plant trees or shrubs near windows to shield from sunlight | $245 | $400 |
$245
4,103
kWh
|
- | |
04 | 2.7221: Lower temperature during the winter season and vice-versa | $5,325 | - |
$5,325
89,097
kWh
|
- | |
05 | 2.2614: Use cooling tower or economizer to replace chiller cooling | $3,124 | $6,200 |
$3,124
52,462
kWh
|
- | |
06 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $354 | $1,072 |
$354
5,862
kWh
|
- | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $8,554 | $18,562 |
$8,890
148,886
kWh
|
$(-336.0) | |
08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $9,444 | $13,440 |
$11,025
184,642
kWh
|
$(-1,581.0) | |
09 | 2.7226: Use computer programs to optimize hvac performance | $4,072 | $1,800 |
$4,072
68,288
kWh
|
- | |
10 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $8,060 | $400 |
$8,060
135,111
kWh
|
- | |
11 | 2.4231: Reduce the pressure of compressed air to the minimum required | $3,056 | $2,000 |
$3,056
51,290
kWh
|
- | |
TOTAL RECOMMENDED | $55,070 | $58,397 |
$56,987
954,864
kWh
|
$(-1,917.0) | ||
TOTAL IMPLEMENTED | $55,070 | $58,397 |
$56,987
954,864
kWh
|
$(-1,917.0) | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs