| Assessment Year | 1992 |
|---|---|
| Principal Product | STRUCTURAL BLOCK |
| NAICS |
n/a
|
| SIC | 3499: Fabricated Metal Products, Not Elsewhere Classified |
| Sales Range | $50 M to 100M |
| # of Employees | 400 |
| Plant Area |
n/a
|
| Annual Production | 500,000
pieces
|
| Production Hrs. Annual | 8,112
hrs
|
| Location (State) | Arizona |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $597,226 | 10,858,734 |
kWh
|
$0.055 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $324,644 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Administrative Changes Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.3415: Use a fossil fuel engine to cogenerate electricity or motive power; and utilize heat | $258,322 | $1,645,200 |
$580,044
10,565,358
kWh
|
$(-163,242.0)
-
MMBtu
|
$(-158,480.0) | |
| 02 | 2.2414: Use waste heat from hot flue gases to preheat | $18,021 | $28,500 | - |
$18,021
-
MMBtu
|
- | |
| 03 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $13,765 | $30,882 |
$13,765
250,293
kWh
|
- | - | |
| 04 | 2.4133: Use most efficient type of electric motors | $2,187 | $9,540 |
$2,187
39,859
kWh
|
- | - | |
| 05 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $1,178 | - |
$1,178
21,395
kWh
|
- | - | |
| 06 | 2.7233: Use properly designed and sized hvac equipment | $10,010 | $349,500 |
$10,010
182,005
kWh
|
- | - | |
| 07 | 2.7422: Plant trees or shrubs near windows to shield from sunlight | $2,715 | $4,900 |
$2,715
49,238
kWh
|
- | - | |
| 08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $11,565 | $17,450 |
$13,110
238,277
kWh
|
- | $(-1,545.0) | |
| 09 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $5,137 | $400 |
$5,137
93,494
kWh
|
- | - | |
| 10 | 2.4312: Improve lubrication practices | $1,744 | $4,914 |
$1,744
31,653
kWh
|
- | - | |
| TOTAL RECOMMENDED | $324,644 | $2,091,286 |
$629,890
11,471,572
kWh
|
$(-145,221.0)
-
MMBtu
|
$(-160,025.0) | ||
| TOTAL IMPLEMENTED | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | Administrative Changes Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs