Assessment Year | 1992 |
---|---|
Principal Product | PHARMACEUTICAL DRUGS |
NAICS |
n/a
|
SIC | 2834: Pharmaceutical Preparations |
Sales Range | $100 M to 500M |
# of Employees | 500 |
Plant Area |
n/a
|
Annual Production | 500,000
pieces
|
Production Hrs. Annual | 5,304
hrs
|
Location (State) | Arizona |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $822,354 | 13,906,800 |
kWh
|
$0.059 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $303,419 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $303,419 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|
01 | 2.4133: Use most efficient type of electric motors | $793 | $6,684 |
$793
13,482
kWh
|
- | - | |
02 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $2,648 | $6,290 |
$2,648
44,842
kWh
|
- | - | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $22,425 | $82,095 |
$22,425
379,250
kWh
|
- | - | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $352 | $1,008 |
$352
5,862
kWh
|
- | - | |
05 | 2.3415: Use a fossil fuel engine to cogenerate electricity or motive power; and utilize heat | $264,625 | $2,031,000 |
$624,765
10,772,568
kWh
|
$(-198,551.0)
-
MMBtu
|
$(-161,589.0) | |
06 | 2.2511: Insulate bare equipment | $264 | $280 | - |
$264
-
MMBtu
|
- | |
07 | 2.1243: Use heat from boiler blowdown to preheat boiler feed water | $2,838 | $7,000 | - |
$2,838
-
MMBtu
|
- | |
08 | 2.2414: Use waste heat from hot flue gases to preheat | $6,956 | $19,000 | - |
$6,956
-
MMBtu
|
- | |
09 | 2.1242: Minimize boiler blowdown with better feedwater treatment | $2,518 | $5,000 | - |
$2,518
-
MMBtu
|
- | |
TOTAL RECOMMENDED | $303,419 | $2,158,357 |
$650,983
11,216,004
kWh
|
$(-185,975.0)
-
MMBtu
|
$(-161,589.0) | ||
TOTAL IMPLEMENTED | $303,419 | $2,158,357 |
$650,983
11,216,004
kWh
|
$(-185,975.0)
-
MMBtu
|
$(-161,589.0) | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs