Assessment Year | 1991 |
---|---|
Principal Product | EXTRUDED ALUMINUM |
NAICS |
n/a
|
SIC | 3354: Aluminum Extruded Products |
Sales Range | $10 M to 50M |
# of Employees | 220 |
Plant Area |
n/a
|
Annual Production | 13,000,000
lb
|
Production Hrs. Annual | 7,488
hrs
|
Location (State) | Arizona |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $756,187 | 12,562,134 |
kWh
|
$0.060 |
Natural Gas | $66,548 | 33,274 |
MMBtu
|
$2.00 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $26,741 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
---|---|---|---|---|---|---|
01 | 2.4133: Use most efficient type of electric motors | $3,399 | $8,199 |
$3,399
56,565
kWh
|
- | |
02 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $7,218 | - |
$7,218
119,871
kWh
|
- | |
03 | 2.2511: Insulate bare equipment | $8,948 | $708 | - |
$8,948
-
MMBtu
|
|
04 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $4,528 | $4,148 |
$4,528
75,322
kWh
|
- | |
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,425 | $100 |
$2,425
40,445
kWh
|
- | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $160 | $53 |
$160
2,638
kWh
|
- | |
08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $63 | $360 |
$63
1,172
kWh
|
- | |
TOTAL RECOMMENDED | $26,741 | $13,568 |
$17,793
296,013
kWh
|
$8,948
-
MMBtu
|
||
TOTAL IMPLEMENTED | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs