Assessment Year | 1998 |
---|---|
Principal Product | Printed Boxes |
NAICS |
n/a
|
SIC | 2653: Corrugated and Solid Fiber Boxes |
Sales Range | $10 M to 50M |
# of Employees | 269 |
Plant Area |
225,000
ft2
|
Annual Production | 20,900
ton
|
Production Hrs. Annual | 5,100
hrs
|
Location (State) | Arkansas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $235,167 | 7,075,909 |
kWh
|
$0.033 |
Electricity Demand | $115,898 | 17,170 |
kW-mo/yr
|
$6.75 |
Natural Gas | $88,840 | 19,911 |
MMBtu
|
$4.46 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $166,945 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $15,905 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Solid Waste (non-haz) Savings | Personnel Changes Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $5,091 | $90 |
$3,957
119,871
kWh
|
$1,134
-
kW-mo/yr
|
- | - | |
02 | 2.4221: Install compressor air intakes in coolest locations | $2,111 | $240 |
$1,601
48,359
kWh
|
$510
-
kW-mo/yr
|
- | - | |
03 | 2.4133: Use most efficient type of electric motors | $1,436 | $160 |
$1,153
26,377
kWh
|
$283
-
kW-mo/yr
|
- | - | |
04 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $2,829 | - |
$2,145
65,064
kWh
|
$684
-
kW-mo/yr
|
- | - | |
05 | 2.7111: Reduce illumination to minimum necessary levels | $1,848 | $240 |
$1,296
39,273
kWh
|
$552
-
kW-mo/yr
|
- | - | |
06 | 3.5315: Lease / purchase baler; sell cardboard to recycler | $5,419 | - |
$(-63.0)
(-293)
kWh
|
- |
$5,776
-
lb
|
$(-294.0) | |
07 | 4.423: Move product using mechanical means | $91,800 | $5,600 | - | - | - | $91,800 | |
08 | 4.423: Move product using mechanical means | $45,680 | $72,000 |
$(-220.0)
(-4,396)
kWh
|
- | - | $45,900 | |
09 | 4.423: Move product using mechanical means | $10,731 | $15,000 |
$(-744.0)
(-15,240)
kWh
|
- | - | $11,475 | |
TOTAL RECOMMENDED | $166,945 | $93,330 |
$9,125
279,015
kWh
|
$3,163
-
kW-mo/yr
|
$5,776
-
lb
|
$148,881 | ||
TOTAL IMPLEMENTED | $15,905 | $730 |
$7,944
233,587
kWh
|
$2,479
-
kW-mo/yr
|
$5,776
-
lb
|
$(-294.0) | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Solid Waste (non-haz) Savings | Personnel Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs