Assessment Year 1996
Principal Product Support Hardware
NAICS
n/a
SIC 3644: Noncurrent-Carrying Wiring Devices
Sales Range $50
M
to 100
M
# of Employees 267
Plant Area 404,000
ft2
Annual Production 6,000,000
pieces
Production Hrs. Annual 6,257
hrs
Location (State) Arkansas

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $249,792 8,390,387
kWh
Electricity Demand $98,694 18,539
kW-mo/yr
Natural Gas $34,737 11,291
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $12,165 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $8,967

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Other Liquid (non-haz) Savings
01 2.4221: Install compressor air intakes in coolest locations $1,369 $20 $1,013
34,877
kWh
$356
-
kW-mo/yr
-
02 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $2,617 $450 $2,024
70,633
kWh
$593
-
kW-mo/yr
-
03 2.4133: Use most efficient type of electric motors $3,695 $5,860 $2,560
88,218
kWh
$1,135
-
kW-mo/yr
-
04 2.4111: Utilize energy-efficient belts and other improved mechanisms $386 - $228
7,913
kWh
$158
-
kW-mo/yr
-
05 2.7142: Utilize higher efficiency lamps and/or ballasts $872 $624 $562
19,343
kWh
$310
-
kW-mo/yr
-
06 2.7111: Reduce illumination to minimum necessary levels $2,326 $2,326 $1,702
58,617
kWh
$624
-
kW-mo/yr
-
07 3.7311: Maintain machines to reduce leaks $900 $300 - - $900
-
gal
TOTAL RECOMMENDED $12,165 $9,580 $8,089
279,601
kWh
$3,176
-
kW-mo/yr
$900
-
gal
TOTAL IMPLEMENTED $8,967 $6,630 $5,825
201,641
kWh
$2,242
-
kW-mo/yr
$900
-
gal
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Other Liquid (non-haz) Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs