Assessment Year | 1996 |
---|---|
Principal Product | Support Hardware |
NAICS |
n/a
|
SIC | 3644: Noncurrent-Carrying Wiring Devices |
Sales Range | $50 M to 100M |
# of Employees | 267 |
Plant Area |
404,000
ft2
|
Annual Production | 6,000,000
pieces
|
Production Hrs. Annual | 6,257
hrs
|
Location (State) | Arkansas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $249,792 | 8,390,387 |
kWh
|
$0.030 |
Electricity Demand | $98,694 | 18,539 |
kW-mo/yr
|
$5.32 |
Natural Gas | $34,737 | 11,291 |
MMBtu
|
$3.08 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $12,165 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $8,967 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Other Liquid (non-haz) Savings |
---|---|---|---|---|---|---|---|
01 | 2.4221: Install compressor air intakes in coolest locations | $1,369 | $20 |
$1,013
34,877
kWh
|
$356
-
kW-mo/yr
|
- | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,617 | $450 |
$2,024
70,633
kWh
|
$593
-
kW-mo/yr
|
- | |
03 | 2.4133: Use most efficient type of electric motors | $3,695 | $5,860 |
$2,560
88,218
kWh
|
$1,135
-
kW-mo/yr
|
- | |
04 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $386 | - |
$228
7,913
kWh
|
$158
-
kW-mo/yr
|
- | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $872 | $624 |
$562
19,343
kWh
|
$310
-
kW-mo/yr
|
- | |
06 | 2.7111: Reduce illumination to minimum necessary levels | $2,326 | $2,326 |
$1,702
58,617
kWh
|
$624
-
kW-mo/yr
|
- | |
07 | 3.7311: Maintain machines to reduce leaks | $900 | $300 | - | - |
$900
-
gal
|
|
TOTAL RECOMMENDED | $12,165 | $9,580 |
$8,089
279,601
kWh
|
$3,176
-
kW-mo/yr
|
$900
-
gal
|
||
TOTAL IMPLEMENTED | $8,967 | $6,630 |
$5,825
201,641
kWh
|
$2,242
-
kW-mo/yr
|
$900
-
gal
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Other Liquid (non-haz) Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs