Assessment Year | 1994 |
---|---|
Principal Product | Engine Nacelles for Commercial Aircraft |
NAICS |
n/a
|
SIC | 3728: Aircraft Parts and Auxiliary Equipment, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 172 |
Plant Area |
135,000
ft2
|
Annual Production | 915
pieces
|
Production Hrs. Annual | 6,257
hrs
|
Location (State) | Arkansas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $275,462 | 3,883,646 |
kWh
|
$0.071 |
Natural Gas | $42,503 | 7,961 |
MMBtu
|
$5.34 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $16,792 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $16,792 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings |
---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,479 | $531 |
$2,479
34,877
kWh
|
|
02 | 2.7111: Reduce illumination to minimum necessary levels | $5,375 | $310 |
$5,375
75,909
kWh
|
|
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,249 | $200 |
$2,249
31,653
kWh
|
|
04 | 2.4133: Use most efficient type of electric motors | $3,176 | $3,090 |
$3,176
44,842
kWh
|
|
05 | 2.3131: Reschedule plant operations or reduce load to avoid peaks | $3,513 | - |
$3,513
-
kWh
|
|
TOTAL RECOMMENDED | $16,792 | $4,131 |
$16,792
187,281
kWh
|
||
TOTAL IMPLEMENTED | $16,792 | $4,131 |
$16,792
187,281
kWh
|
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs