| Assessment Year | 1994 |
|---|---|
| Principal Product | Processed Meat Products |
| NAICS |
n/a
|
| SIC | 2011: Meat Packing Plants |
| Sales Range | $50 M to 100M |
| # of Employees | 700 |
| Plant Area |
175,000
ft2
|
| Annual Production | 50,000,000
lb
|
| Production Hrs. Annual | 6,257
hrs
|
| Location (State) | Arkansas |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $1,042,498 | 16,647,714 |
kWh
|
$0.063 |
| Natural Gas | $261,941 | 83,742 |
MMBtu
|
$3.13 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $114,310 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $65,591 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Personnel Changes Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $1,550 | $1,058 |
$1,550
24,619
kWh
|
- | - | |
| 02 | 2.4133: Use most efficient type of electric motors | $3,660 | $6,380 |
$3,660
58,324
kWh
|
- | - | |
| 03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $735 | $100 |
$735
11,723
kWh
|
- | - | |
| 04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $6,980 | $1,654 |
$6,980
111,372
kWh
|
- | - | |
| 05 | 2.7111: Reduce illumination to minimum necessary levels | $12,331 | $1,730 |
$12,331
196,952
kWh
|
- | - | |
| 06 | 2.1233: Analyze flue gas for proper air/fuel ratio | $33,863 | $1,000 | - |
$33,863
-
MMBtu
|
- | |
| 07 | 2.3131: Reschedule plant operations or reduce load to avoid peaks | $4,438 | $635 |
$4,438
-
kWh
|
- | - | |
| 08 | 2.4134: Replace electric motor with fossil fuel engine | $48,719 | $52,000 |
$68,797
1,098,769
kWh
|
$(-5,078.0)
-
MMBtu
|
$(-15,000.0) | |
| 09 | 2.2511: Insulate bare equipment | $2,034 | $213 |
$2,034
32,532
kWh
|
- | - | |
| TOTAL RECOMMENDED | $114,310 | $64,770 |
$100,525
1,534,291
kWh
|
$28,785
-
MMBtu
|
$(-15,000.0) | ||
| TOTAL IMPLEMENTED | $65,591 | $12,770 |
$31,728
435,522
kWh
|
$33,863
-
MMBtu
|
- | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | Personnel Changes Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs