| Assessment Year | 1994 |
|---|---|
| Principal Product | Crude Cottonseed Oil |
| NAICS |
n/a
|
| SIC | 2074: Cottonseed Oil Mills |
| Sales Range | $10 M to 50M |
| # of Employees | 70 |
| Plant Area |
157,600
ft2
|
| Annual Production | 550,000
Tgal
|
| Production Hrs. Annual | 6,883
hrs
|
| Location (State) | Arkansas |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $678,469 | 12,966,003 |
kWh
|
$0.052 |
| Natural Gas | $541,533 | 142,521 |
MMBtu
|
$3.80 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $21,300 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|
| 01 | 2.4133: Use most efficient type of electric motors | $2,415 | $5,110 |
$2,415
54,807
kWh
|
- | |
| 02 | 2.7111: Reduce illumination to minimum necessary levels | $7,133 | $420 |
$7,133
162,075
kWh
|
- | |
| 03 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $4,129 | $2,544 |
$4,129
93,787
kWh
|
- | |
| 04 | 2.1233: Analyze flue gas for proper air/fuel ratio | $6,867 | $1,000 | - |
$6,867
-
MMBtu
|
|
| 05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $756 | $243 |
$756
17,292
kWh
|
- | |
| TOTAL RECOMMENDED | $21,300 | $9,317 |
$14,433
327,961
kWh
|
$6,867
-
MMBtu
|
||
| TOTAL IMPLEMENTED | - | - | - | - | ||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs