Assessment Year | 2024 |
---|---|
Principal Product | gas distribution products |
NAICS | 334413: Semiconductor and Related Device Manufacturing |
SIC | 3674: Semiconductors and Related Devices |
Sales Range | $100 M to 500M |
# of Employees | 109 |
Plant Area |
74,000
ft2
|
Annual Production | 5,000
pieces
|
Production Hrs. Annual | 4,883
hrs
|
Location (State) | Texas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $99,261 | 1,844,800 |
kWh
|
$0.054 |
Electricity Demand | $31,813 | 3,122 |
kW-mo/yr
|
$10.19 |
Electricity Fees | $14,692 | - |
|
- |
Natural Gas | $17,561 | 1,835 |
MMBtu
|
$9.57 |
TOTAL YEARLY COSTS | $163,327 | |||
RECOMMENDED SAVINGS* | $93,767 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Administrative Changes Savings | Ancillary Material Cost Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.8121: Apply for tax-free status for energy purchases | $39,560 | $5,000 | - | - | $7,912 | - | $31,648 | |
02 | 2.9114: Use solar heat to make electricty | $49,120 | $358,027 |
$49,120
684,000
kWh
|
- | - | - | - | |
03 | 2.3212: Optimize plant power factor | $1,950 | $5,135 | - |
$1,950
-
kW-mo/yr
|
- | - | - | |
04 | 2.7135: Install occupancy sensors | $625 | $240 |
$625
11,600
kWh
|
- | - | - | - | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,512 | $8,350 |
$1,470
27,300
kWh
|
$845
-
kW-mo/yr
|
- | $197 | - | |
TOTAL RECOMMENDED | $93,767 | $376,752 |
$51,215
722,900
kWh
|
$2,795
-
kW-mo/yr
|
$7,912 | $197 | $31,648 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | - |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs