Assessment Year | 2024 |
---|---|
Principal Product | Elementary School Students |
NAICS | 611110: Elementary and Secondary Schools |
SIC | 8211: Elementary and Secondary Schools |
Sales Range | $1 M to 5M |
# of Employees | 50 |
Plant Area |
66,362
ft2
|
Annual Production | 100
units
|
Production Hrs. Annual | 3,888
hrs
|
Location (State) | Texas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $37,076 | 874,435 |
kWh
|
$0.042 |
Electricity Demand | $50,646 | 3,831 |
kW-mo/yr
|
$13.22 |
Natural Gas | $15,152 | 1,464 |
MMBtu
|
$10.35 |
TOTAL YEARLY COSTS | $102,874 | |||
RECOMMENDED SAVINGS* | $37,149 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.7226: Use computer programs to optimize hvac performance | $16,101 | $4,000 |
$10,471
246,962
kWh
|
- |
$5,630
-
MMBtu
|
|
02 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $1,599 | $3,000 |
$845
19,933
kWh
|
$754
-
kW-mo/yr
|
- | |
03 | 2.9114: Use solar heat to make electricty | $16,877 | $327,235 |
$12,488
294,529
kWh
|
$4,389
-
kW-mo/yr
|
- | |
04 | 2.5123: Reduce fluid flow rates | $2,572 | $3,000 |
$2,572
60,699
kWh
|
- | - | |
TOTAL RECOMMENDED | $37,149 | $337,235 |
$26,376
622,123
kWh
|
$5,143
-
kW-mo/yr
|
$5,630
-
MMBtu
|
||
TOTAL IMPLEMENTED | - | - | - | - | - |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs