| Assessment Year | 2024 |
|---|---|
| Principal Product | Newspapers |
| NAICS | 511110: Newspaper Publishers |
| SIC | 2711: Newspapers: Publishing, or Publishing and Printing |
| Sales Range | $5 M to 10M |
| # of Employees | 33 |
| Plant Area |
35,000
ft2
|
| Annual Production | 27,000,000
pieces
|
| Production Hrs. Annual | 4,250
hrs
|
| Location (State) | Texas |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $46,236 | 1,191,303 |
kWh
|
$0.039 |
| Electricity Demand | $48,861 | 4,710 |
kW-mo/yr
|
$10.37 |
| Electricity Fees | $2,053 | - |
|
- |
| Natural Gas | $1,910 | 68 |
MMBtu
|
$28.09 |
| TOTAL YEARLY COSTS | $99,060 | |||
| RECOMMENDED SAVINGS* | $3,455 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,035 | $500 |
$600
14,960
kWh
|
$435
-
kW-mo/yr
|
- | |
| 02 | 2.7141: Lower light fixtures in high ceiling areas | $735 | $1,300 |
$425
10,625
kWh
|
$310
-
kW-mo/yr
|
- | |
| 03 | 2.1321: Replace fossil fuel equipment with electrical equipment | $670 | $790 |
$(-800.0)
(-19,900)
kWh
|
$(-440.0)
-
kW-mo/yr
|
$1,910
-
MMBtu
|
|
| 04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $420 | $7 |
$245
6,070
kWh
|
$175
-
kW-mo/yr
|
- | |
| 05 | 2.7121: Utilize daylight whenever possible in lieu of artificial light | $335 | - |
$130
3,300
kWh
|
$205
-
kW-mo/yr
|
- | |
| 06 | 2.4314: Use synthetic lubricant | $150 | $100 |
$80
1,969
kWh
|
$70
-
kW-mo/yr
|
- | |
| 07 | 2.7135: Install occupancy sensors | $110 | $55 |
$110
2,800
kWh
|
- | - | |
| TOTAL RECOMMENDED | $3,455 | $2,752 |
$790
19,824
kWh
|
$755
-
kW-mo/yr
|
$1,910
-
MMBtu
|
||
| TOTAL IMPLEMENTED | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs