| Assessment Year | 2023 |
|---|---|
| Principal Product | No contact control accessed boxes and cards |
| NAICS | 334515: Instrument Manufacturing for Measuring and Testing Electricity and Electrical Signals |
| SIC | 3669: Communications Equipment, Not Elsewhere Classified |
| Sales Range | $100 M to 500M |
| # of Employees | 350 |
| Plant Area |
250,000
ft2
|
| Annual Production | 20,000,000
pieces
|
| Production Hrs. Annual | 6,109
hrs
|
| Location (State) | Texas |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $451,080 | 7,206,000 |
kWh
|
$0.063 |
| Electricity Demand | $227,013 | 15,412 |
kW-mo/yr
|
$14.73 |
| Electricity Fees | $27,355 | - |
|
- |
| TOTAL YEARLY COSTS | $705,448 | |||
| RECOMMENDED SAVINGS* | $40,642 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $22,780 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Personnel Changes Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.2211: Use optimum temperature | $12,180 | - |
$12,230
195,300
kWh
|
- | - | $(-50.0) | |
| 02 | 2.4239: Eliminate or reduce compressed air usage | $10,660 | $2,690 |
$10,660
170,300
kWh
|
- | - | - | |
| 03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $10,090 | $1,000 |
$7,630
121,900
kWh
|
$2,460
-
kW-mo/yr
|
- | - | |
| 04 | 2.8123: Pay utility bills on time | $2,933 | - | - | - | $2,933 | - | |
| 05 | 2.6218: Turn off equipment when not in use | $2,310 | - |
$2,310
36,890
kWh
|
- | - | - | |
| 06 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,790 | $18 |
$1,390
22,200
kWh
|
$400
-
kW-mo/yr
|
- | - | |
| 07 | 2.4314: Use synthetic lubricant | $350 | $200 |
$240
3,800
kWh
|
$110
-
kW-mo/yr
|
- | - | |
| 08 | 2.7135: Install occupancy sensors | $240 | $480 |
$240
3,830
kWh
|
- | - | - | |
| 09 | 2.7124: Make a practice of turning off lights when not needed | $89 | $38 |
$74
1,180
kWh
|
$15
-
kW-mo/yr
|
- | - | |
| TOTAL RECOMMENDED | $40,642 | $4,426 |
$34,774
555,400
kWh
|
$2,985
-
kW-mo/yr
|
$2,933 | $(-50.0) | ||
| TOTAL IMPLEMENTED | $22,780 | $4,188 |
$19,920
318,230
kWh
|
$2,860
-
kW-mo/yr
|
- | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Personnel Changes Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs