Assessment Year 2022
Principal Product Fungicides
NAICS 325320: Pesticide and Other Agricultural Chemical Manufacturing
SIC 2879: Pesticides and Agricultural Chemicals, Not Elsewhere Classified
Sales Range $50
M
to 100
M
# of Employees 53
Plant Area 72,670
ft2
Annual Production 15,000,000
lb
Production Hrs. Annual 8,496
hrs
Location (State) Texas

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $219,010 5,043,700
kWh
Electricity Demand $75,270 11,400
kW-mo/yr
Electricity Fees $33,814 -
Natural Gas $117,056 42,698
MMBtu
TOTAL YEARLY COSTS $445,150
RECOMMENDED SAVINGS* $156,030 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $156,030

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Electricity Fees Savings Ancillary Material Cost Savings One-time Revenue or Avoided Cost Savings
01 2.8121: Apply for tax-free status for energy purchases $123,505 $10,000 - - $24,701 - $98,804
02 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $12,090 $5,000 $9,520
237,900
kWh
$2,570
-
kW-mo/yr
- - -
03 2.4133: Use most efficient type of electric motors $2,070 $10,152 $1,630
40,741
kWh
$440
-
kW-mo/yr
- - -
04 2.7142: Utilize higher efficiency lamps and/or ballasts $12,720 $29,570 $9,140
228,510
kWh
$2,480
-
kW-mo/yr
- $1,100 -
05 2.4314: Use synthetic lubricant $1,646 $300 $1,296
32,394
kWh
$350
-
kW-mo/yr
- - -
06 2.7111: Reduce illumination to minimum necessary levels $2,835 $1,420 $1,850
46,270
kWh
$985
-
kW-mo/yr
- - -
07 2.4111: Utilize energy-efficient belts and other improved mechanisms $1,164 - $917
22,924
kWh
$247
-
kW-mo/yr
- - -
TOTAL RECOMMENDED $156,030 $56,442 $24,353
608,739
kWh
$7,072
-
kW-mo/yr
$24,701 $1,100 $98,804
TOTAL IMPLEMENTED $156,030 $56,442 $24,353
608,739
kWh
$7,072
-
kW-mo/yr
$24,701 $1,100 $98,804
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Electricity Fees Savings Ancillary Material Cost Savings One-time Revenue or Avoided Cost Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs