Assessment Year | 2021 |
---|---|
Principal Product | Aerospace wiring systems harnesses |
NAICS | 336413: Other Aircraft Parts and Auxiliary Equipment Manufacturing |
SIC | 3728: Aircraft Parts and Auxiliary Equipment, Not Elsewhere Classified |
Sales Range | $100 M to 500M |
# of Employees | 604 |
Plant Area |
120,000
ft2
|
Annual Production | 38,000
pieces
|
Production Hrs. Annual | 2,192
hrs
|
Location (State) | Texas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $146,251 | 2,551,944 |
kWh
|
$0.057 | |
Electricity Demand | $68,318 | 6,324 |
kW-mo/yr
|
$10.80 | |
Electricity Fees | $851 | - |
|
- | |
Waste Disposal Costs | |||||
Water Usage | $2,217 | 372 |
Tgal
|
$5.96 | |
Water Disposal | $2,112 | 372 |
Tgal
|
$5.68 | |
TOTAL YEARLY COSTS | $219,749 | ||||
RECOMMENDED SAVINGS* | $22,970 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | $18,950 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.6218: Turn off equipment when not in use | $11,150 | - |
$11,800
226,300
kWh
|
- | $(-650.0) | - | |
02 | 2.3212: Optimize plant power factor | $4,020 | $16,040 | - |
$4,020
-
kW-mo/yr
|
- | - | |
03 | 2.4239: Eliminate or reduce compressed air usage | $2,300 | $25 |
$1,770
34,000
kWh
|
$530
-
kW-mo/yr
|
- | - | |
04 | 2.7134: Use photocell controls | $2,760 | $460 |
$1,720
33,100
kWh
|
$1,040
-
kW-mo/yr
|
- | - | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,740 | $1,170 |
$370
7,140
kWh
|
$110
-
kW-mo/yr
|
$820 | $1,440 | |
TOTAL RECOMMENDED | $22,970 | $17,695 |
$15,660
300,540
kWh
|
$5,700
-
kW-mo/yr
|
$170 | $1,440 | ||
TOTAL IMPLEMENTED | $18,950 | $1,655 |
$15,660
300,540
kWh
|
$1,680
-
kW-mo/yr
|
$170 | $1,440 |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs