Assessment Year | 2019 |
---|---|
Principal Product | Investment casting, precision machining |
NAICS | 332710: Machine Shops |
SIC | 3599: Industrial and Commercial Machinery and Equipment, Not Elsewhere Classified |
Sales Range | $50 M to 100M |
# of Employees | 45 |
Plant Area |
137,000
ft2
|
Annual Production | 18,000
pieces
|
Production Hrs. Annual | 4,124
hrs
|
Location (State) | Texas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $409,811 | 5,839,900 |
kWh
|
$0.070 | |
Electricity Demand | $84,919 | 15,162 |
kW-mo/yr
|
$5.60 | |
Electricity Fees | $14,839 | - |
|
- | |
Natural Gas | $8,660 | 1,514 |
MMBtu
|
$5.72 | |
Waste Disposal Costs | |||||
Water Usage | $17,769 | 2,194 |
Tgal
|
$8.10 | |
TOTAL YEARLY COSTS | $535,997 | ||||
RECOMMENDED SAVINGS* | $151,643 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | $151,643 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.7232: Replace existing hvac unit with high efficiency model | $122,230 | $353,500 |
$9,290
138,600
kWh
|
$1,940
-
kW-mo/yr
|
- | $111,000 | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $19,281 | $24,231 |
$15,796
235,766
kWh
|
$4,116
-
kW-mo/yr
|
$722 | $(-1,353.0) | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,008 | $2,735 |
$1,008
15,047
kWh
|
- | - | - | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,270 | $680 |
$335
5,010
kWh
|
$42
-
kW-mo/yr
|
$1,275 | $1,618 | |
05 | 2.7135: Install occupancy sensors | $2,875 | $4,200 |
$2,875
42,900
kWh
|
- | - | - | |
06 | 2.7124: Make a practice of turning off lights when not needed | $923 | $100 |
$729
10,876
kWh
|
$194
-
kW-mo/yr
|
- | - | |
07 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,056 | $1,000 |
$1,631
24,357
kWh
|
$425
-
kW-mo/yr
|
- | - | |
TOTAL RECOMMENDED | $151,643 | $386,446 |
$31,664
472,556
kWh
|
$6,717
-
kW-mo/yr
|
$1,997 | $111,265 | ||
TOTAL IMPLEMENTED | $151,643 | $386,446 |
$31,664
472,556
kWh
|
$6,717
-
kW-mo/yr
|
$1,997 | $111,265 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs