Assessment Year | 2018 |
---|---|
Principal Product | extruded cables |
NAICS | 332114: Custom Roll Forming |
SIC | 3496: Miscellaneous Fabricated Wire Products |
Sales Range | $10 M to 50M |
# of Employees | 82 |
Plant Area |
80,000
ft2
|
Annual Production | 76,000
thousand feet
|
Production Hrs. Annual | 6,512
hrs
|
Location (State) | Texas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $57,284 | 962,400 |
kWh
|
$0.060 |
Electricity Demand | $19,978 | 2,004 |
kW-mo/yr
|
$9.97 |
Electricity Fees | $8,713 | - |
|
- |
Natural Gas | $1,311 | 92 |
MMBtu
|
$14.25 |
TOTAL YEARLY COSTS | $87,286 | |||
RECOMMENDED SAVINGS* | $44,825 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $7,335 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Personnel Changes Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.8121: Apply for tax-free status for energy purchases | $32,530 | $3,000 | - | - | $6,506 | - | $26,024 | |
02 | 2.3212: Optimize plant power factor | $4,100 | $9,520 | - |
$4,100
-
kW-mo/yr
|
- | - | - | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,580 | $6,560 |
$2,730
45,900
kWh
|
$850
-
kW-mo/yr
|
- | - | - | |
04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,950 | $11 |
$1,490
25,000
kWh
|
$460
-
kW-mo/yr
|
- | - | - | |
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,065 | $500 |
$815
13,700
kWh
|
$250
-
kW-mo/yr
|
- | - | - | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $510 | $125 |
$85
1,430
kWh
|
$18
-
kW-mo/yr
|
- | $407 | - | |
07 | 2.7124: Make a practice of turning off lights when not needed | $420 | - |
$320
5,410
kWh
|
$100
-
kW-mo/yr
|
- | - | - | |
08 | 2.2511: Insulate bare equipment | $350 | $144 |
$270
4,550
kWh
|
$80
-
kW-mo/yr
|
- | - | - | |
09 | 2.7135: Install occupancy sensors | $320 | $100 |
$320
5,380
kWh
|
- | - | - | - | |
TOTAL RECOMMENDED | $44,825 | $19,960 |
$6,030
101,370
kWh
|
$5,858
-
kW-mo/yr
|
$6,506 | $407 | $26,024 | ||
TOTAL IMPLEMENTED | $7,335 | $7,171 |
$5,675
95,390
kWh
|
$1,660
-
kW-mo/yr
|
- | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Personnel Changes Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs