Assessment Year | 2018 |
---|---|
Principal Product | Structural steel fabrication |
NAICS | 332323: Ornamental and Architectural Metal Work Manufacturing |
SIC | 3446: Architectural and Ornamental Metal Work |
Sales Range | $50 M to 100M |
# of Employees | 75 |
Plant Area |
100,000
ft2
|
Annual Production | 20,156
ton
|
Production Hrs. Annual | 6,864
hrs
|
Location (State) | Texas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $78,624 | 1,876,064 |
kWh
|
$0.042 |
Electricity Demand | $39,986 | 4,886 |
kW-mo/yr
|
$8.18 |
Electricity Fees | $13,713 | - |
|
- |
TOTAL YEARLY COSTS | $132,323 | |||
RECOMMENDED SAVINGS* | $109,420 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $4,285 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.3212: Optimize plant power factor | $7,920 | $17,500 | - |
$7,920
-
kW-mo/yr
|
- | - | |
02 | 2.8121: Apply for tax-free status for energy purchases | $46,750 | $5,000 | - | - | $9,350 | $37,400 | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $37,900 | $117,500 |
$25,700
612,000
kWh
|
$12,200
-
kW-mo/yr
|
- | - | |
04 | 2.4314: Use synthetic lubricant | $4,285 | $300 |
$3,280
78,170
kWh
|
$1,005
-
kW-mo/yr
|
- | - | |
05 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $6,630 | $300 |
$4,730
112,700
kWh
|
$1,900
-
kW-mo/yr
|
- | - | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $5,410 | $12,110 |
$3,860
92,000
kWh
|
$1,550
-
kW-mo/yr
|
- | - | |
07 | 2.4231: Reduce the pressure of compressed air to the minimum required | $245 | $8 |
$135
3,200
kWh
|
$110
-
kW-mo/yr
|
- | - | |
08 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $280 | $300 |
$150
3,500
kWh
|
$130
-
kW-mo/yr
|
- | - | |
TOTAL RECOMMENDED | $109,420 | $153,018 |
$37,855
901,570
kWh
|
$24,815
-
kW-mo/yr
|
$9,350 | $37,400 | ||
TOTAL IMPLEMENTED | $4,285 | $300 |
$3,280
78,170
kWh
|
$1,005
-
kW-mo/yr
|
- | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs