Assessment Year | 2018 |
---|---|
Principal Product | Poultry Processing |
NAICS | 311615: Poultry Processing |
SIC | 2015: Poultry Slaughtering and Processing |
Sales Range | $100 M to 500M |
# of Employees | 1,100 |
Plant Area |
125,000
ft2
|
Annual Production | 68,000,000
pieces
|
Production Hrs. Annual | 6,192
hrs
|
Location (State) | Texas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $1,750,429 | 57,008,433 |
kWh
|
$0.031 |
Electricity Demand | $732,100 | 89,993 |
kW-mo/yr
|
$8.14 |
Electricity Fees | $3,282 | - |
|
- |
Natural Gas | $443,790 | 118,570 |
MMBtu
|
$3.74 |
TOTAL YEARLY COSTS | $2,929,601 | |||
RECOMMENDED SAVINGS* | $128,455 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $45,900 | - |
$30,800
994,400
kWh
|
$15,100
-
kW-mo/yr
|
- | - | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $23,800 | $44,650 |
$15,900
512,200
kWh
|
$7,900
-
kW-mo/yr
|
- | - | |
03 | 2.3212: Optimize plant power factor | $19,915 | $40,190 | - |
$19,915
-
kW-mo/yr
|
- | - | |
04 | 2.1233: Analyze flue gas for proper air/fuel ratio | $15,600 | $2,320 | - | - | - |
$15,600
-
MMBtu
|
|
05 | 2.4231: Reduce the pressure of compressed air to the minimum required | $7,730 | $20 |
$5,160
166,600
kWh
|
$2,570
-
kW-mo/yr
|
- | - | |
06 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $6,060 | $500 |
$4,050
130,800
kWh
|
$2,010
-
kW-mo/yr
|
- | - | |
07 | 2.4314: Use synthetic lubricant | $4,580 | - |
$3,060
98,700
kWh
|
$1,520
-
kW-mo/yr
|
- | - | |
08 | 2.8123: Pay utility bills on time | $2,870 | - | - | - | $2,870 | - | |
09 | 2.7134: Use photocell controls | $2,000 | $1,740 |
$1,170
37,900
kWh
|
$830
-
kW-mo/yr
|
- | - | |
TOTAL RECOMMENDED | $128,455 | $89,420 |
$60,140
1,940,600
kWh
|
$49,845
-
kW-mo/yr
|
$2,870 |
$15,600
-
MMBtu
|
||
TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs