Assessment Year | 2017 |
---|---|
Principal Product | Structural steel fabrication |
NAICS | 332323: Ornamental and Architectural Metal Work Manufacturing |
SIC | 3446: Architectural and Ornamental Metal Work |
Sales Range | $10 M to 50M |
# of Employees | 300 |
Plant Area |
112,000
ft2
|
Annual Production | 2,400,000
lb
|
Production Hrs. Annual | 6,688
hrs
|
Location (State) | Texas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $92,245 | 1,548,152 |
kWh
|
$0.060 |
Electricity Demand | $35,525 | 5,285 |
kW-mo/yr
|
$6.72 |
Electricity Fees | $1,930 | - |
|
- |
TOTAL YEARLY COSTS | $129,700 | |||
RECOMMENDED SAVINGS* | $33,690 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $12,030 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $21,660 | $24,700 |
$17,800
297,000
kWh
|
$3,860
-
kW-mo/yr
|
|
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $10,260 | $500 |
$8,540
142,210
kWh
|
$1,720
-
kW-mo/yr
|
|
03 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,210 | $10 |
$1,010
16,840
kWh
|
$200
-
kW-mo/yr
|
|
04 | 2.7111: Reduce illumination to minimum necessary levels | $560 | $160 |
$430
7,150
kWh
|
$130
-
kW-mo/yr
|
|
TOTAL RECOMMENDED | $33,690 | $25,370 |
$27,780
463,200
kWh
|
$5,910
-
kW-mo/yr
|
||
TOTAL IMPLEMENTED | $12,030 | $670 |
$9,980
166,200
kWh
|
$2,050
-
kW-mo/yr
|
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs