Assessment Year | 2017 |
---|---|
Principal Product | Carbonated beverages, fruit juice, tea |
NAICS | 311421: Fruit and Vegetable Canning |
SIC | 2086: Bottled and Canned Soft Drinks and Carbonated Waters |
Sales Range | $50 M to 100M |
# of Employees | 200 |
Plant Area |
1,424,000
ft2
|
Annual Production | 18,000,000
units
|
Production Hrs. Annual | 7,440
hrs
|
Location (State) | Texas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $436,738 | 6,376,880 |
kWh
|
$0.068 | |
Electricity Demand | $112,956 | 17,161 |
kW-mo/yr
|
$6.58 | |
Electricity Fees | $17,938 | - |
|
- | |
Natural Gas | $135,625 | 27,583 |
MMBtu
|
$4.92 | |
Waste Disposal Costs | |||||
Water Usage | $399,394 | 105,281 |
Tgal
|
$3.79 | |
Water Disposal | $532,862 | 105,281 |
Tgal
|
$5.06 | |
TOTAL YEARLY COSTS | $1,635,513 | ||||
RECOMMENDED SAVINGS* | $76,825 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | $76,825 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Water Usage Savings | Water Disposal Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $16,560 | $2,000 |
$13,450
217,000
kWh
|
$3,110
-
kW-mo/yr
|
- | - | - | - | - | |
02 | 3.4155: Meter waste water | $16,425 | $3,000 | - | - | - | - |
$7,300
-
Tgal
|
$9,125
-
Tgal
|
- | |
03 | 2.8121: Apply for tax-free status for energy purchases | $32,880 | $15,000 | - | - | $6,580 | - | - | - | $26,300 | |
04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $3,370 | $10 |
$2,730
44,000
kWh
|
$640
-
kW-mo/yr
|
- | - | - | - | - | |
05 | 2.7111: Reduce illumination to minimum necessary levels | $2,040 | - |
$1,430
23,100
kWh
|
$610
-
kW-mo/yr
|
- | - | - | - | - | |
06 | 2.2511: Insulate bare equipment | $260 | $271 | - | - | - |
$260
-
MMBtu
|
- | - | - | |
07 | 2.1233: Analyze flue gas for proper air/fuel ratio | $5,290 | $1,720 | - | - | - |
$5,290
-
MMBtu
|
- | - | - | |
TOTAL RECOMMENDED | $76,825 | $22,001 |
$17,610
284,100
kWh
|
$4,360
-
kW-mo/yr
|
$6,580 |
$5,550
-
MMBtu
|
$7,300
-
Tgal
|
$9,125
-
Tgal
|
$26,300 | ||
TOTAL IMPLEMENTED | $76,825 | $22,001 |
$17,610
284,100
kWh
|
$4,360
-
kW-mo/yr
|
$6,580 |
$5,550
-
MMBtu
|
$7,300
-
Tgal
|
$9,125
-
Tgal
|
$26,300 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Water Usage Savings | Water Disposal Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs