| Assessment Year | 2016 |
|---|---|
| Principal Product | Corrugated shipping containers and boxes |
| NAICS | 322211: Corrugated and Solid Fiber Box Manufacturing |
| SIC | 2653: Corrugated and Solid Fiber Boxes |
| Sales Range | $50 M to 100M |
| # of Employees | 120 |
| Plant Area |
300,000
ft2
|
| Annual Production | 96,000
ton
|
| Production Hrs. Annual | 7,224
hrs
|
| Location (State) | Texas |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $581,641 | 8,468,160 |
kWh
|
$0.069 |
| Electricity Demand | $110,253 | 18,249 |
kW-mo/yr
|
$6.04 |
| Electricity Fees | $33,607 | - |
|
- |
| Natural Gas | $343,059 | 66,939 |
MMBtu
|
$5.12 |
| TOTAL YEARLY COSTS | $1,068,560 | |||
| RECOMMENDED SAVINGS* | $245,049 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $227,074 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | One-time Revenue or Avoided Cost Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.8118: Check for accuracy of utility / power meters | $189,624 | - | - | - | $94,812 | $94,812 | |
| 02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $10,440 | $2,000 |
$8,800
127,500
kWh
|
$1,640
-
kW-mo/yr
|
- | - | |
| 03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $11,170 | $800 |
$9,410
136,400
kWh
|
$1,760
-
kW-mo/yr
|
- | - | |
| 04 | 2.3131: Reschedule plant operations or reduce load to avoid peaks | $10,240 | - | - |
$10,240
-
kW-mo/yr
|
- | - | |
| 05 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $10,389 | - |
$7,760
112,459
kWh
|
$2,629
-
kW-mo/yr
|
- | - | |
| 06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $5,600 | $5,030 |
$4,280
62,000
kWh
|
$1,320
-
kW-mo/yr
|
- | - | |
| 07 | 2.4314: Use synthetic lubricant | $5,856 | - |
$4,374
63,393
kWh
|
$1,482
-
kW-mo/yr
|
- | - | |
| 08 | 2.4239: Eliminate or reduce compressed air usage | $760 | $250 |
$760
11,010
kWh
|
- | - | - | |
| 09 | 2.7135: Install occupancy sensors | $970 | $280 |
$970
14,100
kWh
|
- | - | - | |
| TOTAL RECOMMENDED | $245,049 | $8,360 |
$36,354
526,862
kWh
|
$19,071
-
kW-mo/yr
|
$94,812 | $94,812 | ||
| TOTAL IMPLEMENTED | $227,074 | $7,830 |
$22,490
325,900
kWh
|
$14,960
-
kW-mo/yr
|
$94,812 | $94,812 | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | One-time Revenue or Avoided Cost Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs